TROUBLESHOOTING
INNIS01 MODULE EDGE CONNECTORS
WBPEEUI250016A1
5 - 3
A code that is not on the list may appear if a machine fault
time-out occurs. Reset the NPM module if this happens. The
NPM module has failed if the status LED remains red. Replace
the NPM module in this case.
INNIS01 MODULE EDGE CONNECTORS
Tables
through
list the NIS module edge connector pin
assignments.
Table 5-3. INNIS01 Module Edge Connector
P1 Pin Assignments
Pin
Signal
Pin
Signal
1
+ 5 VDC
2
+ 5 VDC
3
Unused
4
Unused
5
Common
6
Common
7
+ 15 VDC
8
- 15 VDC
9
PFI
1
10
PFI
1
11
Unused
12
Unused
NOTE: 1. Power fail interrupt.
Table 5-4. INNIS01 Module Edge Connector
P2 Pin Assignments
Pin
Signal
Pin
Signal
1
Address 1, Data bit 1
2
Address 0, Data bit 0
3
Address 3, Data bit 3
4
Address 2, Data bit 2
5
Address 5, Data bit 5
6
Address 4, Data bit 4
7
Data bit 7
8
Data bit 6
9
Clock
10
Sync
11
Unused
12
Unused