INSTALLATION
UNPACKING AND INSPECTION
3 - 2
WBPEEUI250016A1
®
UNPACKING AND INSPECTION
1. Examine the hardware immediately for shipping damage.
2. Notify the nearest Elsag Bailey sales office of any such
damage.
3. File a claim for any damage with the transportation com-
pany that handled the shipment.
4. Use the original packing material and container to store the
hardware.
5. Store the hardware in an environment of good air quality,
free from temperature and moisture extremes.
INNIS01 NETWORK INTERFACE SLAVE MODULE CONFIGURATION
The process control unit interface requires an INNIS01 Net-
work Interface Slave Module (NIS). Configure the NIS module
dipswitches and jumpers as follows.
Dipswitch Settings
There are four dipswitches on the NIS module. The dipswitches
and their functions are described below. Refer to Figure
for
dipswitch locations.
DIPSWITCH SW1 - NODE ADDRESS
This dipswitch sets the node address. Valid node addresses are
one through 250 (refer to Table
). Pole one is the most sig-
nificant bit with a binary weight of 128. Pole eight is the least