INSTALLATION
INIIR01 INFI-NET TO INFI-NET REMOTE INTERFACE INSTALLATION
3 - 4
I-E96-607A
®
Multi-Function Processor Termination Unit (NTMP01)
instruction or the Multi-Function Processor Termination Mod-
ule (NIMP01/02) instruction for specific directions on configur-
ing jumpers, mounting, termination cable installation, and
RS-232-C cable lengths.
INNIS01 Module Dipswitches
Each INFI-NET to INFI-NET interface requires two INNIS01
Network Interface Slave Modules. For redundant interfaces,
double the required number of INNIS01 modules. There are
four user-configured dipswitches on the network interface
slave (NIS) module. See Figure
for dipswitch locations.
NOTE: Dipswitch positions marked not used or
reserved must be
set to the indicated position, otherwise the INNIS01 module will not
operate properly. Since factory settings may not reflect the default
settings, it is imperative to check all dipswitch and jumper settings
before putting the module into operation.
INNIS01 DIPSWITCH SW1, NODE ADDRESS
This dipswitch sets the resident node address. Valid node
addresses are one through 250 (refer to Table
). Pole one is
the most significant bit (MSB) with a binary weight of 128; pole
eight is the least significant bit (LSB) with a binary weight of
one. Record the dipswitch SW1 setting in the space provided.
INNIS01 DIPSWITCH SW2, LOOP ADDRESS
This dipswitch assigns a loop address to the INNIS01 module
in relation to the main INFI-NET loop. Valid satellite loop
addresses are two through 250. The central loop address must
be one. Refer to Table
, and record the dipswitch SW2 set-
ting in the space provided.
Figure 3-1. INNIS01 Module Circuit Board Layout
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4 5 6 7 8
OPE N
1 2 3 4 5 6 7 8
O PE N
1 2 3 4 5 6 7 8
O PE N
1 2 3 4 5 6 7 8
O PE N
J3
J6
J4
J1
J5
J2
GROUP A
LEDS
GROUP B
LEDS
USER-CONFIGURED
JUMPERS J1-J6
SW3
LOOP MODE
SW1
NODE ADDRESS
T00195A
SW4
I/O EXPANDER
BUS ADDRESS
SW2
LOOP
ADDRESS
P1
P2
P3