INTRODUCTION
I-E96-317A
6 - 1
SECTION 6 - MAINTENANCE
INTRODUCTION
The Remote Input/Output module requires limited mainte-
nance. This section contains a maintenance schedule.
MAINTENANCE SCHEDULE
Perform the tasks in Table
at the specified intervals.
Table 6-1. Maintenance Schedule
Task
Interval
Clean and tighten all power and
ground connection.
Every 6 months or during plant
shutdown, whichever occurs first.
Use a static safe vacuum cleaner
to remove dust from:
Modules
Module Mounting Unit
Fan Assembly
Power Entry Panel
Every 6 months or during plant
shutdown, whichever occurs first.