INSTALLATION
SETUP/PHYSICAL INSTALLATION
I-E96-316A
3 - 3
Analog Output Default Switch (S2)
The analog output default switch (S2), shown in Figure
determines the QRS analog output default values. These are
the values or levels for the analog outputs during system
start-up
(power up
) or bus fault error (
time-out
).
You can select either a 0 percent or 100 percent
power up
out-
put. Selecting 0 percent will output 4 mA or 1 VDC; selecting
100 percent will output 20 mA or 5 VDC. Switch position 3
selects the value for Analog Output 1 (AO1) and position 6
selects the value for Analog Output 2 (AO2). S3 determines the
mode of the output (current or voltage).
If the bus fault timer expires
(time-out
), the digital outputs
de-energize and the analog outputs change to the default value
selected. A
time-out
occurs when the slave does not receive a
clock signal from the MFP. The
time-out
options are to
hold
or
go
to power up state
. The outputs stay at their current values dur-
Table 3-1. Address Switch Settings (S1)
Addr
MSB
LSB
Addr
MSB
LSB
3
4
5
6
7
8
3
4
5
6
7
8
0
0
0
0
0
0
0
32
1
0
0
0
0
0
1
0
0
0
0
0
1
33
1
0
0
0
0
1
2
0
0
0
0
1
0
34
1
0
0
0
1
0
3
0
0
0
0
1
1
35
1
0
0
0
1
1
4
0
0
0
1
0
0
36
1
0
0
1
0
0
5
0
0
0
1
0
1
37
1
0
0
1
0
1
6
0
0
0
1
1
0
38
1
0
0
1
1
0
7
0
0
0
1
1
1
39
1
0
0
1
1
1
8
0
0
1
0
0
0
40
1
0
1
0
0
0
9
0
0
1
0
0
1
41
1
0
1
0
0
1
10
0
0
1
0
1
0
42
1
0
1
0
1
0
11
0
0
1
0
1
1
43
1
0
1
0
1
1
12
0
0
1
1
0
0
44
1
0
1
1
0
0
13
0
0
1
1
0
1
45
1
0
1
1
0
1
14
0
0
1
1
1
0
46
1
0
1
1
1
0
15
0
0
1
1
1
1
47
1
0
1
1
1
1
16
0
1
0
0
0
0
48
1
1
0
0
0
0
17
0
1
0
0
0
1
49
1
1
0
0
0
1
18
0
1
0
0
1
0
50
1
1
0
0
1
0
19
0
1
0
0
1
1
51
1
1
0
0
1
1
20
0
1
0
1
0
0
52
1
1
0
1
0
0
21
0
1
0
1
0
1
53
1
1
0
1
0
1
22
0
1
0
1
1
0
54
1
1
0
1
1
0
23
0
1
0
1
1
1
55
1
1
0
1
1
1
24
0
1
1
0
0
0
56
1
1
1
0
0
0
25
0
1
1
0
0
1
57
1
1
1
0
0
1
26
0
1
1
0
1
0
58
1
1
1
0
1
0
27
0
1
1
0
1
1
59
1
1
1
0
1
1
28
0
1
1
1
0
0
60
1
1
1
1
0
0
29
0
1
1
1
0
1
61
1
1
1
1
0
1
30
0
1
1
1
1
0
62
1
1
1
1
1
0
31
0
1
1
1
1
1
63
1
1
1
1
1
1
1= OPEN ; 0=CLOSED