INTRODUCTION
SPECIFICATIONS
I-E96-211A
1 - 7
Nomenclature of the Termination Units
SPECIFICATIONS
Name
Nomenclature
Function
Termination Unit*
NTMF01
Provides link to Control Stations and redundant
MFCs. Provides Serial Ports for Basic, C and
sequential event recorder.
Termination Module*
NIMF01 NIMF02 Provides link to Control Stations and redundant
MFCs. NOTE: Termination modules are
high-density versions of the termination units.
Cables
NKTU01 (TU)
NKTU02 (TM)
NKTM01 (TM)
NKMF02 (no TU)
Standard module to termination module cable.
Connects primary MFC to redundant MFC.
* Termination units/modules are required if a Control Station is being used for Basic and C programming or for a
sequential event recorder. In other cases, only the NKMF02 cable (for redundancy) is required.
Microprocessor
68020
Memory
512 Kbytes of RAM
80 Kbytes of Battery Backed RAM (non-volatile)
256 Kbytes of UVROM
Communication Ports
(2) RS-232-C - Serial
(2) RS-422 - SAC/DCS Link, MFC to MFC redundancy
Power Consumption
4.5 Amps nominal at +5 VDC (23 Watts)
37 mA nominal at +15 VDC (0.6 Watts)
18 mA nominal at -15 VDC (0.3 Watts)
Power Dissipation
37.68 Watts maximum
Mounting
Occupies two slots in standard Infi 90 Module Mounting Unit (MMU).
Environmental
Ambient Temperature
0
o
to 70
o
C (32
o
to 158
o
F)
Relative Humidity
5% to 95% up to 55
o
C (131
o
F) (non-condensing)
5% to 45% at 70
o
C (158
o
F) (non-condensing)
Atmospheric Pressure
Sea level to 3 km (1.86 miles)
Air Quality
Noncorrosive
Certification
CSA certified for use as process control equipment in an ordinary
(nonhazardous) location.
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE