TROUBLESHOOTING
OFF-LINE FAILURE
6 - 8
I-E96-322A
®
OFF-LINE FAILURE
This part of the troubleshooting section covers off-line failures
and how to troubleshoot those failures. Off-line failures occur
during module calibration and are a result of improper or
incomplete installation or calibration.
If the HSS module fails to calibrate after completing the instal-
lation procedure:
1. Locate the cause of the failure using the troubleshooting
flowchart in Figure
.
2. Refer to Table
for corrective action.
Figure 6-3. Off-Line Failure Troubleshooting Flowchart
(Page 1 of 3)
START
DONE
DONE
CALIBRATE
LVDT AND
ACTUATOR?
CONFIGURATION
ERRORS?
FC 150 SET FOR
CALIBRATION?
CALIBRATE
LVDT AND
ACTUATOR?
YES
YES
NO
NO
YES
YES
NO
NO
READ FC 55 OR 150
BLOCK OUTPUTS AND
REQUEST MODULE
PROBLEM REPORTS
VERIFY FC 55 OR 150
IS SET FOR
CALIBRATION
CHECK HARDWARE
INSTALLATION
REMOVE HSS
MODULE FROM
MMU
A1
TP25416A