INTRODUCTION
SPECIFICATIONS
1 - 8
WBPEEUI240752A0
®
Magnetic and electromagnetic
fields
(continued)
Radio-frequency common mode,
amplitude modulated, 0.15 MHz
to 80 MHz
(ENV 50141)
Unmodulated rms: 10 V/m
Amplitude modulated: 80% AM (1 kHz)
Source impedance: 150
Ω
Emission test
RF radiated fields, 30 MHz to 1000
MHz (ENV 55011)
Class A
CE Mark Declaration
EMC 89/336/EEC
Low Voltage Directive 73/23/EEC
This product, when installed in an INFI 90 OPEN cabinet, complies
with the following directives/standards requested for CE marking:
EN50081-2 Generic Emission Standard - Part 2: Industrial
Environment
EN50082-2 Generic Immunity Standard - Part 2: Industrial
Environment
EN 61010 Safety Requirements for Electrical Equipment for
Measurement, Control and Laboratory Use - Part 1: General
Requirements
Certifications
CSA (Canadian Standards Associ-
ation)
FM (Factory Mutual) (pending)
Certified for use as process control equipment in an ordinary
(non-hazardous) location per CSA C22.2 No. 1010.1-92
Approval for the following categories.
Nonincendive for:
Class I, Division 2, Groups A,B,C,D
Class II, Division 2, Groups F,G
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE.
Table 1-5. Specifications
Property
Characteristic/Value