INSTALLATION
I-E96-225A
3 - 7
way in redundant mode. Refer to Figure
for the schematic
of jumpers J11 and J12.
DIPSWITCH SETTINGS
The module has two configurable dipswitches, SW2 and SW3.
The dipswitches have eight poles. Refer to Figure
for loca-
tions. The poles of each dipswitch are numbered 1 through 8.
The IMCPM03 module has two modes:
•
Normal operation mode
.
(includes SPM/CPM02 mode and database mode)
•
Diagnostic mode
.
Normal operation mode
-
Normal operation mode occurs
whenever the module is not operating in the diagnostic mode.
Additionally, the normal operation mode provides for the
IMCPM03 to operate in either the SPM/CPM02 mode or the
database mode. These selections are accomplished by setting
dipswitches SW2 and SW3. Dipswitch SW2 sets a variety of
module options in this normal operating mode, e.g., LED dis-
play, database mode, command/reply checksums, etc.
Dipswitch SW3 sets the operation mode (normal or diagnostic),
module communication mode and the module address.
Figure 3-6. Schematic Diagram of
Jumpers J11 and J12
TP36058B
MODULE BUS A
MODC
JMODA
J11
P1-11
1
2
3
MODULE BUS B
JMODB
J12
P1-4
3
1
2
CAUTION
Only qualified personnel should configure these dipswitches.
Damage or misoperation could occur if dipswitches are
improperly configured.
ATTENTION
Seulement un personnel qualifié devrait configurer ces
micro-interupteurs. Un mauvais fonctionnement ou des dom-
mages pourraient se produire suite à une mauvaise configura-
tion des micro-interupteurs.