INTRODUCTION
I-E96-207A
A - 1
APPENDIX A - TERMINATION UNIT CONFIGURATION
(NTCS02)
INTRODUCTION
The IMCOM03/04 uses an NTCS02 for termination. It handles
four analog inputs, two analog outputs, three digital inputs
and four digital outputs. Dipshunts on the Termination Unit
(NTCS02) configure the I/O.
NOTE: There is no dipshunt socket to configure for the digital out-
puts on the NTCS02.
The Controller Termination Unit (NTCS02) and Cable (NKTU01)
provide the interface from the field connections to the control-
ler module. The TCS consists of four terminal blocks, nine dip-
shunts and sockets, fuses and limiting resistors (see Figure
). The terminal blocks correspond to fixed function blocks
(analog input/outputs and digital inputs/outputs). The dip-
shunts are configured to match the field input type, current or
voltage.
Figure A-1. NTCS02 Termination Unit
TB4
TB2
8
9
10
6
5
4
3
2
1
7
8
9
10
6
5
4
3
2
1
7
8
9
10
6
5
4
3
2
1
7
8
9
10
6
5
4
3
2
1
7
TB1
TB3
XU9
XU8
XU6
XU5
XU7
T00120A
E3
E2
E4
E1
F2, 1A
F3, 4A
F1, 4A
P3
P2
P4
P5
P1
XU4
XU3
XU2
XU1
P4 SOCKET TO ENABLE
TERMINATION UNITS TO
CONNECT TOGETHER, SIMILAR
SOCKET (P5) LOCATED AT UPPER
LEFT OF P3 CONNECTOR
P2 CONNECTOR FOR CONTROL
STATION, SIGNAL 1
POWER SUPPLY
CONNECTIONS
(I/O POWER)
POWER SUPPLY
CONNECTIONS
(DIGITAL INPUT)
P3 CONNECTOR
FOR CONTROL
STATION, SIGNAL 2