INSTALLATION
SETUP
I-E96-207A
3 - 3
SETUP
NOTE: These procedures must be performed before operating the
module.
Configure the controller module according to your specific
application. Module address, power up voltage levels and time
out values for analog outputs, and digital input values are
user-configurable, and set by dipswitches S2, S3, S4, and
jumpers J1 through J3. Figure
shows the location of these
components.
Switch Settings
There are four switches on the circuit board. They are S1 (reset
switch), S2 (analog output number 1), S3 (analog output num-
ber 2), and S4 (module address and self-test routines).
Refer to Table
and Figure
for the settings of S2 and S3.
Refer to Table
and Figure
for the settings of S4.
NOTE: Digital outputs are zero during start-up and during operator
selected RESET or STOP.
Figure 3-1. Switch and Jumper Locations
T00113A
STATUS LED
RESET SWITCH
(S1)
ROMS
ANALOG OUTPUT
DIPSWITCHES
(S2 AND S3)
DIGITAL INPUT
JUMPERS
ADDRESS/TEST
DIPSWITCH (S4)
1
8
6
6
1
1
OPEN
OPEN
OPEN
U3
S3
U4
S2
J1
J2
P3
P1
J3
Table 3-1. Switch S2/S3 Analog Output Settings
Analog Output Number 1 Switch S2
Switch
Position
Open
(1 - off)
Closed
(0 - on)
Function
1
X
Yields 5.25 VDC output for power up.
X
Yields 0.75 VDC output for power up.
2
X
Holds last analog output value on time
out.
3
X