INSTALLATION
INSTALLATION
2 - 4
WBPEEUI210501A0
®
To install the cable:
1. Turn the IMDSO04/14 module latching screws ½-turn
either way to release them.
2. Pull the IMDSO04/14 module out several inches from the
module mounting unit backplane.
3. Insert the J2 end of the cable into the module mounting
unit backplane slot assigned to the IMDSO04/14 module.
4. Insert the J1 end of the cable into the P1 connector on the
relay assembly board.
5. Insert the IMDSO04/14 module into the module mounting
unit until the rear edges are firmly seated in the backplane
connectors.
6. Turn the two latching screws ½-turn either way to lock the
module into the module mounting unit.
Relay
Relays are included with the relay assembly and should
already be installed.
To install a relay:
1. Verify the relay is the same type listed in Table
5-1
.
2. Align the keyed center prong of the relay with the keyed
center hole of the relay socket.
3. Push the relay into the relay socket until it is firmly seated.
4. If the optional hold down spring is installed, position the
wire clip over the relay to secure the relay to the board.
CAUTION
Use only Elsag Bailey approved relays on the relay assembly.
Using unapproved relays could improperly route signals and
damage equipment connected to the relay and the relay itself.
CSA certification is voided when unapproved relays are used.
ATTENTION
N'utilisez que des relais approuvés par Elsag Bailey sur les
panneaux de relais standard. Sinon, les signaux risquent d'être
acheminés de façon inadéquate et ainsi endommager l'équipe-
ment relié au relais ou le relais lui-même. La certification CSA
n'est pas valable lorsqu'on utilise des relais non approuvés.