INSTALLATION
SETUP/PHYSICAL INSTALLATION
3 - 4
WBPEEUI240757A0
®
Analog Output Jumpers (J1 through J28)
Jumpers J1 through J28 configure the analog output mode
(current or voltage) for outputs 1 through 14. Current mode is
four to 20 mA; voltage mode is one to five VDC. Figure
shows the jumper locations on the ASO board. Determine the
output mode requirements for each analog output for your
application; set jumpers to the positions shown in Table
.
Each jumper has a left pin, center pin and right pin. For cur-
rent, position the jumper on the left and center pins (1-2). For
voltage, the jumper would be on the center and right pins (2-3).
Termination Unit/Module Configuration
A TU/TM connects the field device wiring to the INFI 90 OPEN
system. The terminal blocks (connection points) are located on
the TU/TM. You must configure the TU/TM to output the ASO
module signals that are sent to the process field device. Refer
to the appendices to determine the configuration for your
application.
Figure 3-1. Analog Output Module
MODULE STATUS LEDS
ANALOG OUTPUT
ADDRESS SWITCH
T00943A
1
8
OPEN
S1
P1
P3
P2
EDGE
CONNECTORS
CURRENT
VOLTAGE
J1
J2
J3
J4
J5
J6
J7
J8
J9
J10
J11
J12
J13
J14
J15
J16
J17
J18
J19
J20
J21
J22
J23
J24
J25
J26
J27
J28
Figure 3-2. Address Select
Switch (S1)
1
2
3
4
5
8
6
7
OPEN
MUST
REMAIN
CLOSED
I/O
ADDRESS
MSB
LSB
TP65205B
NOTE: OPEN POSITION = LOGIC 1