Modbus Registers
All of the following are available as Input Registers . Data is formatted as a float (CD AB) and each data point isstored in two
Modbus registers .
Addr Function
1
Flow 1 Rate (GPM)
3
Flow 2 Rate (GPM)
5
Flow 1 Total (gallons)
7
Flow 2 Total (gallons)
9
Energy Rate (BTU/min)
11
Energy Total (BTU)
13
Batch 1 Count
15
Batch 2 Count
17
Temp 1 (deg F)
19
Temp 2 (deg F)
21
Temp Delta (T2-T1)
USB Port
Use
Standard Cable
USB Type A Male
to
Type Mini B 5 Pin Male
Connect to
Computer USB
Com Port
Figure 16: USB analog output
OTEE:
N
Communication via the USB port requires a terminal emulator . This port is part of the
Analog Output Option
card . See
"USB Communication" on page 26
for instructions on how to use this port .