WIRING INSTRUCTIONS
Wiring Terminals
1
2
3
4
5
6
7
8
Figure 3: Wiring terminals
Terminal
Function
Operation
1
DC common
—
2
Count input
NPN signal, 280 Hz max or
Dry contact, 95 Hz max
3
—
Not used
4
Remote reset
Resets count value when switched to common .
5
Front panel program enable
Allows access to program mode when connected to common .
6
Solid-state relay
Pulse output (+)
7
Solid-state relay
Pulse output (–)
8
DC supply input
10…28V DC for backlighting and/or powering the output .
Table 1: Wiring terminals
Transmitter Connections
For connecting to Badger Meter transmitters, refer to the literature for your specific transmitter and to
below . The
Connections
column refers to the wires on the transmitter . The numbers in parentheses refer to the terminal numbers on the
ER-9 . Connect the wire coming from the transmitter to the corresponding terminal number for the ER Remote models .
Connecting to a Generic Reed Switch
To connect a generic reed switch to the ER-9, connect one of the wires to terminal 1 and the remaining wire to terminal 2 .
Connecting to a Generic NPN Transmitter
To connect a generic NPN transmitter to the ER-9, connect the emitter to terminal 1 . Connect the collector to terminal 2 .
Transmitter
Connections
Transmitter
Connections
FT-1 (1/2 in . OP)
Black (1)
Black (2)
PFT-2
White (1)
White (2)
FT-1
White (1)
White (2)
PFT-2E
Black (1)
Green (2)
FT-1E
Black (1)
Green (2)
PFT-3E
Black (1)
Green (2)
FT-2
White (1)
White (2)
PFT-3
White (1)
White (2)
FT-420
Black (1)
White (2)
PFT-420
Black (1)
White (2)
MS-E1
Black (1)
Red (2)
PFT-420/2
Black (1)
White (2)
MS-E5
Black (1)
Red (2)
PFT-4E
Term 6 (1)
Term 5 (2)
PFT-1E
Term 6 (1)
Term 5 (2)
PM-5
Black (1)
Red (2)
Table 2: Transmitter connections
User Manual
Page 7
August 2018
REG-UM-00836-EN-12