Piping Configurations and Transducer Positioning

Figure 2

 shows the number of pipe diameters required downstream and upstream of the transducers for various 

piping configurations.

Flow

Flow

Flow

14

5

Flow

Flow

Flow

10

5

10

5

24

5

10

5

24

5

Figure 2:  Piping configuration and transducer positioning

The system will provide repeatable measurements on piping systems that do 

not

 meet these pipe diameter requirements, but 

the accuracy of the readings may be influenced.

Mounting Configuration

The mounting configuration for these transducers is

 V

-Mount, where the sound traverses the pipe twice. 

V

-Mount is a 

compromise between travel time and signal strength.

TOP VIEW

OF PIPE

Figure 3:  V-mount configuration

The frequency setting depends on the pipe material. 

Pipe Size

Frequency 

Setting

TFX-500w/TFX-5000 

Transducer

Pipe

1/2 in.

2 MHz

D*-*-CA

ANSI

D*-*-CG

Copper

D*-*-CM

Stainless Steel

3/4 in.

2 MHz

D*-*-CB

ANSI

D*-*-CH

Copper

D*-*-CN

Stainless Steel

1 in.

2 MHz

D*-*-CC

ANSI

D*-*-CT

Copper

D*-*-CP

Stainless Steel

1-1/4 in.

2 MHz

D*-*-CD

ANSI

D*-*-CJ

Copper

D*-*-CQ

Stainless Steel

1-1/2 in.

2 MHz

D*-*-CE

ANSI

D*-*-CK

Copper

D*-*-CR

Stainless Steel

2 in.

1 MHz

D*-*-CF

ANSI

D*-*-CL

Copper

2 MHz

D*-*-CS

Stainless Steel

Table 1: Transducer frequency settings