background image

Wall Mount Installation
Badger Meter does not currently offer a wall mount enclosure for this product . However, Series 3100 flow monitors can be 

wall mounted in the field into any appropriate customer-supplied enclosure . 

Electrical Power

MPORTANT

I

Before applying power to this unit, check the Model # label: The Series 3100 flow monitor can be ordered as low voltage 12…24V AC/

DC (3100-0x) or as high voltage 120/240V AC (3100-1x).

Low Voltage 12…24V AC/DC Wiring
The Series 3100 flow monitor has a green, three-terminal connector with screw heads, and requires 12…24V AC/DC to 

operate . See 

"Specifications" on page 30

 for the current DC draw and AC Volt-Amp requirements . Always use a fused circuit . 

Connect the positive end of the power supply to the Series 3100 flow monitor terminal marked LV AC/DC (+), and connect 

the negative end of the power supply to the Series 3100 flow monitor terminal marked LV AC/DC (–) . Earth ground can be 

connected to the terminal marked EARTH .

Ground should be heavy gauge wire and as

short as possible.

If panel mounting in a metal enclosure,

Ground to door and bond the door to the

enclosure across the hinges with a brad

just long enough to allow the door to 

open freely.

Orange Label

Earth Ground

LV AC/DC (+)

LV AC/DC (-)

3

2

1

AC         AC

12 . . . 24V AC

Power Supply

(+)        (-)

12 . . . 24V DC

Power Supply

Either AC or DC power can be used.

AC is not polarity sensitive.

Figure 3:  Series 3100-0x low voltage power supply wiring

High Voltage Power Supply Wiring
The Series 3100-1x is designed to accept a standard EL-712 (NEMA 5-15R) plug similar to those used on many laptop 

computers . Power can be 120…240V AC 50…60 Hz . When the High Voltage option is ordered (3100-1x), a power cord is 

supplied with the unit .
See 

"Specifications" on page 30

 for volt/amp ratings for inverter or other non-conventional source .

Installation

Page 7 

October 2017

CTL-UM-01026-EN-05

Summary of Contents for Data Industrial 3100 Series

Page 1: ...Industrial Flow Monitor Series 3100 CTL UM 01026 EN 05 October 2017 User Manual...

Page 2: ...Industrial Flow Monitor Series 3100 Page ii October 2017 CTL UM 01026 EN 05...

Page 3: ...puts Solid State Switch or Sine Wave 8 Analog Input 9 Output Wiring 9 Mechanical Form C Relays COM N O and N C 9 Normally Open Solid State Switch 11 Analog Outputs 11 RS485 Communication Wiring 12 USB...

Page 4: ...otalizer Pulse Output 23 Setpoints 23 Communication 24 RS485 COM Port Configuration 24 Modbus 24 BACnet 25 USB Command List 26 Troubleshooting 29 Trouble Codes 29 Specifications 30 Ordering Matrix 31...

Page 5: ...latile memory no battery backup is required Two independent pulse and analog input channels can be used separately or combined in addition or subtraction modes for all display output functions Field d...

Page 6: ...ow monitor generates very little heat so no consideration need be given to cooling or ventilation However prolonged direct sunlight can damage the front panel so some level of shading is recommended e...

Page 7: ...nd of the power supply to the Series 3100 flow monitor terminal marked LV AC DC Earth ground can be connected to the terminal marked EARTH Ground should be heavy gauge wire and as short as possible If...

Page 8: ...lassical K pulses gal values for calibration Pullup K Factor Provides an internal pullup resistor and uses classical K pulses gal values for calibration Sine K Factor Accepts zero crossing low voltage...

Page 9: ...ane 2 Input ranges of 0 1V DC 0 5V DC 0 10V DC 1 20 mA or 4 20 mA can be selected from front panel or via USB communication port 3 Voltage inputs are high impedance 100 K Current inputs are 100 Ohm As...

Page 10: ...lay 1 NC Relay 1 COM Relay 2 NO Relay 2 NC Relay 2 COM Relay 3 NO Relay 3 NC Relay 3 COM Relay 4 NO Relay 4 NC Relay 4 COM Pulse 1 OUT Pulse 1 OUT Sensor Input Card Red Label 14 Pin Connector 1 2 3 4...

Page 11: ...ing If additional source voltage is required an external source of up to 30V DC can be used Analog Input Device 12V max 20 mA Analog Analog NOTEE Resistor only required for voltage input devices 0 1V...

Page 12: ...Shield Series 3700 or other Modbus or BACnet Master Device Figure 11 RS485 communication wiring Modbus BACnet USB Communications Port Using the USB Port requires Windows HyperTerminal or other similar...

Page 13: ...sed by pressing the MENU Button One each screen there are three Choices In this case RESET SETUP and DIAG selects RESET selects SETUP and selects DIAG RESET SETUP DIAG Main Setup screen accessed by pr...

Page 14: ...Enter Set point 1 00000000 Menu Enter Figure 13 Selection screen Option List Screens Units of measure is an example of an options list Press to scroll up the list and to scroll down through the list...

Page 15: ...User Manual INTENTIONAL BLANK PAGE Page 15 October 2017 CTL UM 01026 EN 05...

Page 16: ...low 1 Rate Flow 1 Total Flow 2 Rate Flow 2 Total Flow 1 2 Rate Flow 1 2 Total Flow 1 2 Rate Flow 1 2 Total Flow 2 1 Rate Flow 2 1 Total Update rate 0 00000000 sec 9 99999999 sec Appears only if Setup...

Page 17: ...1 2 29 Serial XXXXXX Error codes 000 000 000 000 SETUP RLY3 RLY4 Pulse SETUP AOUT1 AOUT2 COMM Go to RS485 MODBUS BACnet Go to Analog Outputs Go to Relays Pulse Outputs Go to Flow Inputs SETUP FLOW2 RL...

Page 18: ...acre ft min acre ft hr bbl s bbl min bbl hr Custom units Flow total units gal Mgal L ft3 m3 acre ft bbl Custom units Custom units LABEL CONV Flow X total UNITS DIG CUST Flow 1 digits 0 1 2 Flow X tot...

Page 19: ...0000 sec Flow 1 timeconst 0 00000000 sec 100 000000 sec DI sensor K num 0 00000000 999999999 K Factor 0 00000000 999999999 DI Sensor Cal KNUM OFFSET DI Sensor Offset 999999999 0 00000001 0 00000001 99...

Page 20: ...ate units gal Mgal L ft3 m3 acre ft bbl Custom units Totalizer input Flow 1 Total Flow 2 Total Flow Sum Total Flow 1 2 Total Flow 2 1 Total 1 pulse 0 00000001 999999999 Time closed 0001 ms 9999 ms Rel...

Page 21: ...FACTRY Adjust 20 mA 60748 FACTRY Analog output 1 FUNC RANGE SCR Analog output 1 UNITS SETPT P Analog output 1 I D LOW Analog output 1 HIGH Analog output 1 CAL Analog output range 0 to 20 mA 4 to 20 mA...

Page 22: ...ADDR MAX DEVID Baud Rate Auto 9600 19200 38400 76800 MSTP Address 001 127 Comm NET BAUD ADDR Baud Rate 300 1200 2400 9600 19200 38400 76800 MODBUS Address 001 247 Network MODBUS Network BACnet MSTP De...

Page 23: ...int crossing before restarting the count from zero LATCH Locks relay in energized state If Latch is chosen once energized by the setpoint time delay the relay remains energized until a reset is select...

Page 24: ...Modbus Network RS485 Baud Rate Selectable Protocol RTU or ASCII Addresses 001 to 247 Slave only Read Input Registers 30001 39999 Function 04 Data Type IEEE 754 Float ABCD CDAB Each variable is stored...

Page 25: ...pin USB connector is also included As much as possible the commands mimic the use of the front panel controls To use this feature the following are required PC with USB ports and Windows HyperTermina...

Page 26: ...lay line1 1 sets Line 1 of the display to display 1 which is the totalizer for flow channel 1 Diagnostics id show model number software version echo on off turn on off interactive command line with ec...

Page 27: ...low rate min current flow 1 2 sensor avg 0 100 averaging time constant in seconds flow 1 2 rate units 0 19 flow channel rate units to display 0 GPM 1 gal s 2 gal hr 3 Mgal day 4 L s 5 LPM 6 L hr 7 ft3...

Page 28: ...1 5 rate x totalizer rate relay 1 5 ctime 0 10000 pulse width in milliseconds relay 1 4 latch on off turn on off relay latching relay 1 4 setpoint x relay 1 4 setpoint x relay 1 4 relpoint x relay 1...

Page 29: ...reading from analog input AD converter channel 1 32 Error reading from analog input AD converter channel 2 36 Error writing to analog input AD converter channel 1 37 Error writing to analog input AD...

Page 30: ...ourcing Sinking 30V DS 0 mA max 3 V 20 mA min Sourcing 600 max load USB Communication Provides complete access to all programming and operation features Requirements USB 2 0 A to Mini B five pin cable...

Page 31: ...nitor Ordering Matrix Example 3100 1 0 Series Flow Monitor 3100 Power Supply Low Voltage 0 12 24V AC VDC High Voltage 1 120 240V AC Mounting Panel Mount 0 Figure 4 Ordering matrix Ordering Matrix Page...

Page 32: ...a Guadalupe Inn CP 01050 M xico DF M xico 52 55 5662 0882 Europe Eastern Europe Branch Office for Poland Latvia Lithuania Estonia Ukraine Belarus Badger Meter Europe ul Korfantego 6 44 193 Knur w Pola...

Reviews: