Baccara landscape 

| solenoids

Problem

Cause

Check

Solution

The controller does 

not perform flushing 

(Automatic or Manual)

1. No water

1. Check the inlet pressure 

and the system flowrate

1. Make sure that the water 

supply (or the pump) is on.

2. Empty Battery

2. Check the battery

2. Replace the battery

3. Incorrect DP settings - 

High

3. Check the DP across the 

filtration system.  

If it is lower than the 

setting, make sure it is 

increasing over time.  

If not check the filters 

integrity.

3. Lower the DP setting to 

appropriate valve for the 

specific water quality and 

dirt load.

4. No control pressure

4. Check the control tubes 

filter for clogging

4. Clean the control tubes 

filter

The controller backwashes 

constantly

1. Incorrect DP settings - Low 1. Check if the DP is set too 

low

1. Set the DP to 0.5 bar

2. Sensor not zeroed

2. Disconnect the upstream 

and downstream tubes 

and check that the 

pressure indicated in the 

octopus app is 0

2. Disconnect the upstream 

and downstream tubes 

and perform ‘Zero offset’ 

from the advanced 

settings screen

Valve does not  

open / close

1. The valve number selected 

is incorrect

1. Check the valve number 

1. Select the correct valve 

number

2. Faulty solenoid

2. Check the solenoid

2. Replace the solenoid

3. No control pressure

3. Check the control tubes’ 

filter for clogging

3. Clean the control tubs’ 

filter

4. Faulty flushing valve

4. Check the valve 

4. Service or replace the 

valve

Valves open instead of 

closing and close instead 

of opening

1. Solenoid valves in reverse 

polarity

2. check if the solenoids 

are connected in reverse 

polarity

3. Reverse the solenoids 

connections polarity

TROUBLESHOOTING

Summary of Contents for G75-DFC

Page 1: ...G75 DFC A U T O M A T I O N C O N T R O L Tackling climate change together Differential Filtration Controller Installation Operation Maintenance IOM...

Page 2: ...part any part of this document or its content The confidential nature of and or privilege in the file enclosed is not waived or lost as a result of a mistake or error in this file If you received this...

Page 3: ...Waterproof Small Wire Connector LV9000 8 DryConn 22 to 12 AWG Wire Connectors 8 Provided by DryConn 8 BATTERY INSTALLATION 9 Before installing the battery 9 Replacing the battery 9 The User Interface...

Page 4: ...replacing a Low Battery icon appears on screen Technical Data Controller Set Supplied with DFC controller suitable for DC only and one analog sensor Mechanical Operating temperature 10 C to 60 C Outdo...

Page 5: ...vant standards and regulations Electrical wiring should be performed by an authorized electrician only using standardized and approved components and tools Locate the G75 DFC Filtration Controller whe...

Page 6: ...ontroller The G 75 DFC Main Components Electric cable Pipe fitting Mounting screws x 2 Pipe fitting Controller D Upper digits UD Lower digits LD DP Pipe fitting Mounting screws x 2 Controller DFC disp...

Page 7: ...e Connects to the black wire of solenoid number 3 filter valve 3 Black wire of the Differential Pressure switch DP Switch Installation Connect the controller s molded cable with the 3 wire connector t...

Page 8: ...ed connection Do not reuse DryConn 22 to 12 AWG Wire Connectors Provide by DryConn 1 Strip 22 18 wires 1 2 12 7mm And 16 12 wires 3 8 9 5mm 2 Align any frayed strands or conductors 3 Pre twisting unne...

Page 9: ...k the cover and secure the four screws The LCD display shows The actual differential pressure DIF The pressure set point SET The flushing cycles counter FC While in flushing a Faucet icon appeases on...

Page 10: ...the controller is paused such as off season or when controlling the filters is not required In the OFF mode the lower line of the controller LD displays OFF In this mode the controller stops reading t...

Page 11: ...samples shortens The maximal interval time between readings is 60 seconds while the minimal interval time between readings is 5 seconds The delay between filters during flushing Off time between valve...

Page 12: ...the above process for filters number 2 and 3 2 Using the and the keys adjust the minutes If A is selected press SET to complete the setting 3 Press SET to continue 4 Using the and the keys adjust the...

Page 13: ...y 1 Incorrect DP settings Low 1 Check if the DP is set too low 1 Set the DP to 0 5 bar 2 Sensor not zeroed 2 Disconnect the upstream and downstream tubes and check that the pressure indicated in the o...

Page 14: ...yer shall deliver the product to one of Baccara s facilities and collect it from the same facility once repair is completed G75 DFC 22 04 21 Page 15 of 15 Warranty Baccara Geva ACS Ltd Baccara product...

Page 15: ...15 G75 DFC Differential Filtration Controller IOM IOM...

Page 16: ...3 9553 4963 F 61 0 3 9553 4965 Cheltenham Victoria 3192 Australia australia baccara geva com www baccarageva com au Store www baccarastore com au BACCARA Espa a C Marqu s de Monteagudo N 24 Madrid T 3...

Reviews: