Tie rod & straps for combined inlet shields
1.
Turn-buckle
2.
Tie straps
3.
Inside view of unit
3. To remove the combined inlet shields, lift each section and pull at the lower end.
Remove combined inlet shields
4. Reinstall the cleaned combined inlet shields.
5. Reinstall tie rod.
6. The supporting steel strip does not need to be reinstalled because it is only required for safe transport
purposes.
7. Make sure the profile of the combined inlet shields keeps the water inside the unit. The correct position is with
the horizontal part towards the outside of the unit and the sloping part facing downwards to the inside of the
unit.
W W W . B A L T I M O R E A I R C O I L . E U
29
5 Maintenance Procedures
5 Maintenance Procedures