The LON Variables page lists the network variables found in the device just learned. Initially
all of the check boxes will be unchecked, and the register number boxes will be
empty (contain zero). This is where you choose which variables you will map to which local
registers.
Start by clicking the check boxes to select the variables you want mapped. You may then
click the "Auto Allocate" button to have X2 pick registers for you. It will pick floating point or
integer registers based on what the variable type is inside the LonWorks device. You can
select registers manually if desired.
Once you have completed these steps, the variables are now mapped. Our over simplified
example below shows that we are only going to retrieve a single phase of volts, plus
frequency, from a WattNode Plus. Assuming the device is connected, you are now polling for
data. Click on the LON Data tab to go look at the data.