In order to guarantee permanent readiness for operation of the B-SAFETY eye showers it is recommended that

the showers are subjected to a regular (at least annual) and comprehensive service. Within the framework of this

service the shower's closing characteristics must be examined and checks must be made to establish any leaks

and contamination such as e.g. dust or calcium deposits.
The hose of the hand-held eye showers must be examined for possible twists, kinks or other forms of damage.

Defective parts must be replaced immediately. The back flow preventer which is installed in the connection piece

must be renewed every two years.

11.2 Care

In the event of contamination or calcium deposits the shower should be cleaned properly with a suitable cleaning

agent which is not aggressive towards the fittings and then rinsed with water following use. High pressure cleaners

must not be used.
In EX environments any plastic surfaces must be cleaned by gently wiping it with a damp or antistatic cloth.

12. Faults

It is possible that hand-held eye showers may leak following connection to the cold water pipe. This is generally

due to impurities from the water system which settle in front of the valve. In this case disconnect the hand-held

eye shower from the water supply. Activate the shower without pressure a few times and rinse the pipe thoroughly

prior to reconnection.

13. Disposal

The safety shower system can be fully dismantled. The individual sections such as metal, insulation etc. can be

sent for recycling separately. The national and local waste disposal regulations must be observed. 

B-SAFETY GmbH

Grützmühlenweg 46 • DE 22339 Hamburg

Tel. +49-(0)40/53 80 92-70 •  Fax. -86

[email protected] • www.b-safety.com

B-SAFETY - Tip!
Functional test

Extensive service

Interval

weekly

annually

Execution

user

specialist

Benefit

=> Protection against contamination (regular change of

the standing water)

=> Ensuring the short-term readiness for operation of the

shower
=> Ensuring the continuous readiness for operation of

the shower

Fault

Water quantity too low

Shower is leaking

Shower is leaking

Shower does not switch off automati-

cally

Possible cause

=> Water pressure or diameter of the

feed pipe too low
=> Strainer filter contaminated
=> Flow regulator defective
=> The valve is not closing properly  

=> Valve seal is damaged

=> This is NOT a fault. According to

standards this is required.

Possible solution

=> Test the piping system

=> Clean the strainer filter
=> Change the flow regulator
=> Check the valve stop for damage

and ensure that the valve is pressed

back into a completely closed position.

=> Change the valve

=> This is NOT a fault. According to

standards this is required.

Operating Instructions for ClassicLine / PremiumLine Eye Showers  B-SAFETY 