Installation and Operating Instruction for
B.E.G.
- Occupancy detectors PD9-M-DALI/DSI-FC und PD9-M-DALI/DSI-GH-FC
Unlocking device
Lock device
LUXOMAT
®
PD9-M-DALI/DSI(-GH)
1b. Mounting preparations
Work on the 230 V mains supply
may only be carried out by quali-
fied professionals or by instructed
persons under the direction and
supervision of qualified skilled
electrical personnel in accordance
with electrotechnical regulations.
Disconnect supply before installing!
When in Master/Slave mode of
operation, the Master-appliance
must always be installed at the
location where there is least
daylight.
Switching between DSI and DALI program
Factory setting DSI, press 1x DALI, press 2x DSI
(Toggle-function)
Luminance set point for constant light regulation
+ / –
small steps
+
/
–
big steps
Dimming
The following approach will prove useful when setting a
command value (example workplace): Place a luxmeter flat
on the desk, then, using the remote control IR-PD-DALI, adjust
the light up or down by pressing the keys max or min until
the desired command value which best suits your require-
ments has been reached.
Automatic reading in the current light value
as new luminance set point
Individual light value 2 - 2500 Lux
Follow-up time (relay and channel 1)
1 upto 30 min.
Orientation lighting and its follow-up time
OFF button:
No orientation light
Grey button:
Programming the switch-off delay time
On button:
Orientation light is permanently activated.
Note:
During the orientation light phase, the constant light reg-
ulation is also active: if there is sufficient brightness, dimming
occurs < 2 V and, if applicable, the lighting is switched off.
Preset/user mode => (see page 2, point 8)
Fully automatic/semi automatic mode => (see page 2, point 7)
Semi automatic: green LED,
Fully automatic: red LED on for ca. 3 sec.
Resetting when open
All values which have been programmed using the remote
control IR-PD-DALI are deleted, and those values which have
been set by potentiometer are activated.
Lock device
Test mode
Reset to deactivate
Resetting when closed
The lighting relay is switched off, i.e.
opened and the follow-up times reset.
Permanent protection against sabotage
This function blocks the unit permanently (green LED is
illuminated). This operating mode can only be activated
during the period of 5 seconds after pressing the “lock“
button. This status will only permit actuating the function
“Light on/Light off”.
The procedure for leaving this mode is as follows:
1. Switch off the current
2. Apply current for 31 - 59 seconds
3. Switch of the current again
4. Apply current
5. Open detector
Light on/off => (see page 2, point 9)
The light will remain switched on/off for as long as move-
ments are detected in the areas of coverage. Once the last
movement has been detected, the light will remain on for
the duration of the follow-up time as per setting.
The appliance will then return independently to the mode
selected (Fully or Semi-automatic).
1a. Features
* For connection of up to 12 lamps
* Suitable for dimmable electronic
ballasts and control modules
* DALI/DSI output
* Constant light control
* Manual switching/dimming
* Semi or completely automatic
operation
* Luminance (brightness) set point,
switch-off delay time for LIGHT and
orientation-light adjustable
* Sensor and power sections in one
housing
* Infrared remote control
max
50
Lux
1500
Lux
ON
OFF
max
50
Lux
1500
Lux
ON
OFF
max
50
Lux
1500
Lux
ON
OFF
max
50
Lux
1500
Lux
ON
OFF
max
50
Lux
1500
Lux
ON
OFF
max
50
Lux
1500
Lux
ON
OFF
max
50
Lux
1500
Lux
ON
OFF
max
50
Lux
1500
Lux
ON
OFF
20 %
max
50
Lux
1500
Lux
ON
OFF
+–
DSI/
DALI
2a. Installation LUXOMAT
®
PD9-M-
DALI/DSI(-GH)-FC
The detector has
been designed and
developed specifi-
cally for installation in
suspended ceilings.
A circular opening of
diameter min. 34 mm
must be produced in
the ceiling.
Having connected the cables in accordance with
the regulations, connect the power supply via the
RJ11 plug. Therefore, open the power supply with
the help of the screws and close it afterwards. After
that, put the power supply through the opening in
the ceiling and mount the sensor onto the ceiling
according to figure.
3. Settings carried out
using remote control
(optional)
Remote control LUXOMAT
®
IR-PD-DALI
Check Battery:
Open battery compartment
by pressing the plastic
springs together and remo-
ving the battery-holder.
The
LUXOMAT
®
PD9-M-
DALI/DSI(-GH) enters an
initial 60-second self-test
cycle, when the supply
is first connected. The
occupancy detector is
ready for operation.
2b. Self test cycle
Option:
Wall bracket for remote control
IR-PD-DALI
Walking across
Walking towards
Seated
6. Range of Coverage
PD9-M-DALI/DSI
5. Dimensions
PD9-M-DALI/DSI
PD9-M-DALI/DSI-GH
PD9-M-DALI/DSI-GH
4. Exclude sources of
interference
PD9-FC
PD9-GH-FC
In case the sensing area of the
LUXOMAT
®
PD9-M-DALI/DSI(-GH) is
too large or areas are being covered
that should not be monitored, the range
can be reduced or limited through use
of the enclosed masking clips.
Overview range in dependence from the mounting
height
Mounting
height
Range (circular detection) T=18°C
walking across
5.00 m
Ø=3.00 m
6.00 m
Ø=3.50 m
7.00 m
Ø=4.20 m
8.00 m
Ø=4.80 m
9.00 m
Ø=5.40 m
10.00 m
Ø=6.00 m
GB
10 m
6 m
2.50 m
10 m
360°
2.50 m