Installation and Operating Instruction for
B.E.G.
-
Occupancy detectors
PD9-M-2C
3. PD9-M-2C:
Settings carried out
using remote control
(optional)
Remote control
LUXOMAT
®
IR-PD-2C
1. Check Battery:
Open battery compartment
by pressing the plastic springs
together and removing the
battery-holder.
1. Mounting preparations
Work on the 230 V mains supply
may only be carried out by quali-
fied professionals or by instructed
persons under the direction and
supervision of qualified skilled elec-
trical personnel in accordance with
electrotechnical regulations.
Disconnect supply before installing!
When in Master/Slave mode of
operation, the Master-appliance
must always be installed at the
location where there is least
daylight.
2a. Installation
Option:
The
LUXOMAT
®
PD9-M-1C
+HVAC enters an initial
60-second self-test cycle,
when the supply is first con-
nected. The occupancy detec-
tor is ready for operation.
2c. Self test cycle
B.E.G.
LUXOMAT
®
PD9-M-2C
2b. Connecting terminals
7. Range of Coverage
In case the sensing area of the
LUXOMAT
®
PD9-M-2C is too large or
areas are being covered that should not
be monitored, the range can be reduced
or limited through use of the enclosed
masking clips.
6. Exclude sources of
interference
1
Walking across
2
Walking towards
3
Seated
quer zum Melder gehen
frontal zum Melder gehen
Unterkriechschutz
PD9-M-2C
8. Dimensions
HKL
max
.
3A
N
L‘
L
S
R
Sensor
OUT
IN
165 mm
24 mm
24 mm
45
25
12
16
PD9-M-2C
GB
10 m
6 m
4 m
10 m
360°
2,50 m
RJ
2
3
1
Wall bracket for remote control
IR-PD-2C
An adhesive film for the surface of the
IR-PD-2C is included with the device. If
required, this can be used for any
B.E.G.
remote control with 27 keys.
In order to benefit from the whole range
of functions of the PD9-M-2C, please
order separately the remote control
IR-PD-2C.
IR-PD-2C - 92475
4. Settings by remote control IR-PD-2C
Unlocking device – Activation of the
programming mode
Locking device – Exit programming mode
The device is not suited for safe disconnection of the
mains supply
Change between fully automatic and semi
automatic mode (HA)
Luminance set point for channel 1
20 - 1000 Lux
Automatic reading in the current light value as
new luminance set point
Change between motion detector and
photo electric switch
Increase the current light level by
20 resp 50 Lux
Light ON/OFF
Resetting when
open:
Deletes all
values set with
the remote con-
trol, light OFF.
After reset the
default settings
are activated.
(500 Lux, 10 min
light channel and
15 min HVAC
channel)
or
1000
20
to
+
Follow-up time channel 1 (light)
5 - 30 min. or impuls
Follow-up time channel 2 (HVAC)
5 - 120 min. or impuls
to
LED ON/OFF (by holding down the push button)
Detection sensitivity reduced or normal
Daytime operation, detector only
activated by motion
or
PI R
CdS
Permanent protection against sabotage
white LED flashes
w
hen c
hoo
sing CdS
or
��
���
120
min
5
min
max
50
Lux
1500
Lux
ON
OFF
t < 5 s
��
���
5
min
��
���
��
���
HA
ON/OFF
The detector has been
designed and developed
specifically for installation
in suspended ceilings.
A circular opening of
diameter min. 34 mm
must be produced in the
ceiling.
Having connected the
cables in accordance with the regulations, connect the
power supply via the RJ12 plug. Therefore, open the
power supply with the help of the screws and close it
afterwards. After that, put the power supply through the
opening in the ceiling and mount the sensor onto the
ceiling according to figure.
34 mm
5. Key functions in closed state
Light ON/OFF during the detection of
motion plus follow-up time; Activation
of the 12 h-ON/OFF-function by
holding down the push button
Switches channel off and is immedi-
ately active again, exits all timers,
interruption of light measurement
Permanent protection against sabotage
This function blocks the unit perma-
nently. This operating mode can only be
activated during the period of 5 seconds
(white LED flash) after pressing the “Lock“
button. The procedure for leaving this
mode is as follows:
1. Switch off the current
2. Apply current for 31 - 59 seconds
3.
Switch off the current again
4. Apply current, wait for selftest
cycle
5.
Open detector
Changes to “open” state
Activation/Deactivation of the test
function
Confirmation
t < 5 sec.
max
50
Lux
1500
Lux
ON
OFF