background image

Connection of sensor and power supply by means of R J12

Power supply:

  

230 V~ ±10 %

Power consumption:

  

< 1W

Degree of protection/class:

  

IP20 / II 

Settings:    

by remote control

Light values:

  

20 - 1000 Lux

Extension of the detection area:

  

with Slaves

Area of coverage:

  

circular 360°

Range Ø H 2.50m/T=18°C:

 

seated 4.00m / tangential  

 

 

10 m / radial 6 m

Recommended height for mounting

   2 - 3 m

Light measurement:

  

daylight and artificial light

• One channel to switch the lighting

Type of contact:

  

 NOC/with pretravel tungsten 

contact

Contact load:

  

2300 W cos

ϕ

=1 / 

 

 

1150 VA cos

ϕ

= 0.5

Time-settings:

   

5 min

.

 - 30 min. / test

• 

Channel 2 for control devices (only reacts on motion)

Contact load:

 

230V~, 3 A cos

 ϕ

=1, μ-Contact

Follow-up time:

  

 5min. - 120min. with time delay 

of 5min. for follow-up time > 

15min./

Alarm impulse

Dimensions H x Ø [mm]

PD9-M-2C: 

Ø 36 x H 28 mm

Power supply 

L165 x W 24 x H 24 mm

Technical data PD-Slave

Power supply:

 230 V~ 

±

10 %

Impulse output:

  

Optocoupler max. 2 W

Impulse duration:

  

2 sec. or 9 sec.

Dimensions:

 

see above

 

Declaration of Conformity: 

The product complies with the low 

voltage recommendation 2006/95/EC and the EMV recommendation 

2004/108/EC.

18. Technical data

Type

RAL9010

RAL9006

PD9-M-2C (Master)

92976

PD9-S-FP (Slave)

92905

92906

LUXOMAT

®

 Remote control:

IR-PD-2C 

 92475 

IR-PD-Mini 

 92159

Accessory:

Cover ring for PD9  white 

92238

Cover ring for PD9  silver 

92237

Cover ring for PD9  anthracite 

92235

16. Article / Part-Nr. / Accessory

MAN 7

67

– 

02

10

15

–1

17. LED-functional indicators, fault-finding

The functional indicators in the case of the 

LUXOMAT

®

 PD9-

M-2C (red and green LED‘s)

Red LED indicating self-checking mode (over a period of 60 

seconds following mains‘-supply lock-on)

 

Flashing at intervals of 1 second

  

EEPROM/memory empty

Flashing rapidly

 

EEPROM/memory contains information

Red LED as an indicator of status

 

Flashing irregularly

 

Movements are detected within the area of coverage

Flashing regularly

 

 Detector identifies bright, light off  

(dependent upon operating mode)

Not illuminated

 

 Detector identifies darkness, light on  

(dependent upon operating mode)

Flashing extremely rapidly

 

Too bright / Too dark / Undefined

Red LED as an acknowledgement of receipt for  

commands from the remote control 

Illuminated for 2 seconds

 

Signal validly received

Illuminated for 0.5 seconds

 

 Command not accepted, detector blocked

Flashing extremely rapidly

 

 

 Command not accepted, occurs, for example, when an 

attempt is made to input twilight-value are too bright or too 

dark
Lights up for 3 seconds 

Display

 

automatic: Lights up for 3 seconds

Flashing for 3 seconds 

 

Display

 

semi automatic

Green LED as an indicator of status for

 

 “Permanent protection against sabotage”

 

Flashing irregularly

 

 Movement are detected within the area of coverage

Flashing regularly

 

 Detector identifies bright, light off  

(dependent upon operating mode)

Not illuminated

 

 Detector identifies darkness, light on  

(dependent upon operating mode)

lluminated for 2 seconds 

Signal validly received  

(only possible for status “Light on/Light off”)