Connection of sensor and power supply by means of R J12
Power supply:
230 V~ ±10 %
Power consumption:
< 1W
Degree of protection/class:
IP20 / II
Settings:
by remote control
Light values:
20 - 1000 Lux
Extension of the detection area:
with Slaves
Area of coverage:
circular 360°
Range Ø H 2.50m/T=18°C:
seated 4.00m / tangential
10 m / radial 6 m
Recommended height for mounting
2 - 3 m
Light measurement:
daylight and artificial light
• One channel to switch the lighting
Type of contact:
NOC/with pretravel tungsten
contact
Contact load:
2300 W cos
ϕ
=1 /
1150 VA cos
ϕ
= 0.5
Time-settings:
5 min
.
- 30 min. / test
•
Channel 2 for control devices (only reacts on motion)
Contact load:
230V~, 3 A cos
ϕ
=1, μ-Contact
Follow-up time:
5min. - 120min. with time delay
of 5min. for follow-up time >
15min./
Alarm impulse
Dimensions H x Ø [mm]
PD9-M-2C:
Ø 36 x H 28 mm
Power supply
L165 x W 24 x H 24 mm
Technical data PD-Slave
Power supply:
230 V~
±
10 %
Impulse output:
Optocoupler max. 2 W
Impulse duration:
2 sec. or 9 sec.
Dimensions:
see above
Declaration of Conformity:
The product complies with the low
voltage recommendation 2006/95/EC and the EMV recommendation
2004/108/EC.
18. Technical data
Type
RAL9010
RAL9006
PD9-M-2C (Master)
92976
—
PD9-S-FP (Slave)
92905
92906
LUXOMAT
®
Remote control:
IR-PD-2C
92475
IR-PD-Mini
92159
Accessory:
Cover ring for PD9 white
92238
Cover ring for PD9 silver
92237
Cover ring for PD9 anthracite
92235
16. Article / Part-Nr. / Accessory
MAN 7
67
9
–
02
10
15
–1
17. LED-functional indicators, fault-finding
The functional indicators in the case of the
LUXOMAT
®
PD9-
M-2C (red and green LED‘s)
Red LED indicating self-checking mode (over a period of 60
seconds following mains‘-supply lock-on)
Flashing at intervals of 1 second
EEPROM/memory empty
Flashing rapidly
EEPROM/memory contains information
Red LED as an indicator of status
Flashing irregularly
Movements are detected within the area of coverage
Flashing regularly
Detector identifies bright, light off
(dependent upon operating mode)
Not illuminated
Detector identifies darkness, light on
(dependent upon operating mode)
Flashing extremely rapidly
Too bright / Too dark / Undefined
Red LED as an acknowledgement of receipt for
commands from the remote control
Illuminated for 2 seconds
Signal validly received
Illuminated for 0.5 seconds
Command not accepted, detector blocked
Flashing extremely rapidly
Command not accepted, occurs, for example, when an
attempt is made to input twilight-value are too bright or too
dark
Lights up for 3 seconds
Display
automatic: Lights up for 3 seconds
Flashing for 3 seconds
Display
semi automatic
Green LED as an indicator of status for
“Permanent protection against sabotage”
Flashing irregularly
Movement are detected within the area of coverage
Flashing regularly
Detector identifies bright, light off
(dependent upon operating mode)
Not illuminated
Detector identifies darkness, light on
(dependent upon operating mode)
lluminated for 2 seconds
Signal validly received
(only possible for status “Light on/Light off”)