B.E.G. LUXOMAT PD4-M-DIM-Corridor Installation And Operating Instruction Download Page 2

18. Technical data PD4-M-DIM-C

15. Wiring diagrams

MAN 7

26

– 

05

031

4–3

In case the sensing area of the 

LUXOMAT

®

 PD4-M-DIM-C 

is too large or areas are being covered that should not be 

monitored, the range can be reduced or limited through 

use of the enclosed masking clips (e).

14. Exclude sources of interference

13. Range

10.  Fully / Semi automatic mode

(for IR-PDim functions see page 1)

The system switches over when the “Light” push-button is 

open (see remote control functions, page 1). Each time 

a push-button is pressed, the current operating mode is 

indicated:

Red lights for 3 sec.  

= Fully automatic mode

Green lights for 3 sec.   = Semi-automatic mode 

Fully automatic operation

In this operating mode, the lighting switches automatically 

on and off for increased comfort, depending on presence 

and brightness.

Semiautomatic operation

In this operating condition, in order to gain increasedsav-

ings, the lighting is energized only after being manually 

switched on. Switch-off takes place automatically. 
The semiautomatic mode basically behaves like the fully 

automatic. However, the difference is that switching-on must 

always be carried out manually!
As many (closer-contact) buttons as desired can be wired in 

parallel on the “S” button input (ON/OFF Dimm).

19. LED-functional indicators, fault-finding

The functional indicators in the case of the 

LUXOMAT

®

 

PD4-M-DIM-C (red and green LED‘s) 

Red LED indicating self-checking mode 

(over a period of 60 seconds following mains‘-supply lock-on)

Flashing at intervals of 1 second

EEPROM

/memory empty

Flashing rapidly

EEPROM

/memory contains information

Red LED as an indicator of status

Flashing irregularly

Movements are detected within the area of coverage

Flashing regularly

Detector identifies bright, light off (dependent upon operating mode)

Not illuminated

Detector identifies dark, light on (dependent upon operating mode)

Flashing extremely rapidly

Too bright / Too dark / Undefined

Red LED as an acknowledgement of receipt for commands from the 

remote control

Illuminated for 2 seconds

Signal validly received

Illuminated for 0.5 seconds

Not-accepted command, detector blocked

Flashing extremely rapidly

Not-accepted command, occurs, for example, when an attempt
is made to input twilight-value are too bright or too dark

Green LED as an acknowledgement of receipt for commands from 

the remote control

Lights up for 3 seconds

Semi automatic or user signal correctly received

Green LED as an indicator of status 

(only for status “Permanent protection against sabotage”)

Flashing irregularly

Movement are detected within the area of coverage

Flashing regularly

Detector identifies bright, light off (dependent upon operating mode)

Not illuminated

Detector identifies dark, light on (dependent upon operating mode)

lluminated for 2 seconds

Signal validly received (dependent upon operating mode)

White LED

Lights permanently

Semi-automatic active (shines)

Illuminates 4 seconds, then 1 sec off

Semi-automatic and active corridor

Illuminates 1 seconds, then 4 sec off

Only active corridor

e

WE RECOMMEND THAT BEFORE DIMMING OF THE CONNECTED 

LIGHTS A 100 h BURN IN (T5 TUBES OR 80 HOURS FOR T8 TUBES) 

FUNCTION TAKES PLACE. 
THE LIFESPAN OF THE LAMPS CAN BE REDUCED IF THE BURN IN 

DOES NOT TAKE PLACE.

max

50

Lux

1500

Lux

ON

OFF

max

50

Lux

1500

Lux

ON

OFF

12. Manual Switching 

You can switch the lighting on and off manually by 

pressing the pushbutton for a short time. It will stay on or 

off as long as people are detected plus the confi gured 

follow up time.

40 m

20 m

8 m 24 m

3 m

5 m

20 m

20 m

20 m

5 m

5 m

2.50 m

1

2

1

Walking across
Walking towards

2

17. Article / Part nr. / Accessory

16. Connections

Typ

SM

FC

FM

PD4-M-DIM-C (Master)

92218

92217

PD4-S-C (Slave)

92442

92444

92445

LUXOMAT

®

 Remote control:

IR-PDim (incl. wall bracket) 

92200

IR-PD-DIM-Mini  

92098

Accessory:

BSK Ball basket guard  

92199

Occupancy detectors – Covering IP23 

92206

SM-Wall bracket 

 

92441

PD4-M-DIM-C-FC

PD4-M-DIM-C-SM socket

L

N

R

Slave

L'

L

S

N

N

– +

R

T1

N

L

+

E1 

1-10 V 

EB

Sensor and power supply in one case

Power supply:

  

230 V~ 

±

10 %

Power consumption:

  

< 1W

Ambient temperature:

  

-25°C to +50°C

Degree of protection/class:

   SM IP54, FC and FM IP20 / II / 

Settings:   

  

locally and by remote control

Light values - IR-PDim:

  

50 - 1500 Lux

Extension of the detection area:

 

with Slaves

Area of coverage:

  

 narrow detection area, ideal for 

corridors

Range of coverage Ø H 2.50 m / T = 18°C:

  

 

tangential 40 m / radial 20 m

Height for mounting:

  

2 - 3 m

Light measurement:

  

 Mixed light, da artificial light 

Lux values - Potentiometer:

   10 - 2000 Lux

• Channel 1 for light-connection

Type of contact:

 

 NOC/with pretravel tungsten contact

Contact load:

  

 2300 W cos

ϕ

=1 / 

1150 VA cos

ϕ

= 0.5, µ-Contact 

Time-settings:

  

1 - 30 min. / Test

DIM-Output:

  

1 x (1-10 V)

Max. no. of series-connected electronic ballasts: 

max. 50 electronic ballasts by one single supply with 

max. 100 m cable run and a conductur cross-section of 

0.75 mm²

Dimensions H x Ø [mm]

 SM  FC  FM

PD4-M-DIM-C 

65 x 98  103 x 97  84 x 97

Visible portion when built into ceiling:

  30 x 97 mm

Technical data PD4-Slave-C

Power supply:

  

230 V~ 

±

10 %

Impulse output:

  

Optocoupler max. 2 W

Impulse duration:

  

2 sec. or 9 sec.

Dimensions:

 

see above

 

Declaration of Conformity: 

The product complies with the low 

voltage recommendation 2006/95/EC and the EMV recommen-

dation 2004/108/EC.

L

N

R

Slave

L'

L

S

N

– +

R

T1

N

L

+

E1 

1-10 V 

EB

11.  Manual Dimming – Preset /User

(for IR-PDim functions see page 1)

Manual dimming – 

Start the dim process by pressing the 

push button „min/max“. Stop by pressing the push button 

„eye“. 

PRESET – 

the luminance set point is set during start-up 

operation by the installer and remains unchanged. The 

luminance set- point confi gured through manual dimming is 

only applied for the time being. 

Caution: 

The constant light regulation is now deactivated!

The currently set artifi cial light is retained independent of 

the ambient/daylight brightness!

After switching off and then back on, the originally set 

luminance set-point is reset = constant light regulation is 

activated.

USER

The luminance set-point is changed upon each manual dim-

ming and re-adjusted by the user (Conformation through 

relay clicking!) The constant light regulation remains 

activated!

The system switches over when the “Doublelock” push-button 

is open (see remote control functions, page 1). Each time 

a push-button is pressed, the current operating mode is 

indicated:

Red lights for 3 sec.  

= Preset

Green lights for 3 sec.   = User

max

50

Lux

1500

Lux

ON

OFF

Standard mode with master DIM occupancy detectors

















L

N

E1     110 V EB

N

L

+

R

S

L L΄΄΄΄

N

+

N L

R

T1

C1

optional

T1 = NO button for semi-automatic mode
Slave for enlargement of detection area