12 m
12 m
8 m
6.40m
24 m
360°
2.50 m
19. Technical data PD4-M-3C-TRIO
Sensor and power supply in one case
Power supply:
230 V~
±
10 %
Power consumption:
< 1W
Ambient temperature:
-25°C – +50°C
Degree of protection /class:
IP20 / II
Settings:
control dial, DIP switch and remote control
Light values-Remote control:
100 - 1000 Lux
Extension of the detection area:
with Slaves
Area of coverage:
circular 360°
Range of coverage Ø H 2.50 m / T=18°C:
seated 6.40m / tangential 24 m / radial 8 m
Recommended height for mounting:
2 - 3 m
Mixed light measurement:
da artificial light measurement
Lux values-Potentiometer:
10 - 2000 Lux
• Channel 1-3 for light-connection, light controlled
Type of contact:
NOC/with pretravel tungsten contact
Contact load:
3000 W, cos
ϕ
=1 / 1500 VA,
cos
ϕ
= 0.5,
µ
-Contact
Time-settings:
5 - 90 min. / Test with remote control
1 - 60 min. / Test with potentiometer
Dimensions H x Ø [mm]
SM
FC
PD4-M-3C-TRIO
124 x 85 100 x 117
Visible portion when built into ceiling:
H 37 x Ø 117mm
Technical data PD4-Slave
Power supply:
230 V~
±
10 %
Impulse output:
Optocoupler max. 2 W
Impulse duration:
2 sec. or 9 sec.
Dimensions:
see above
Declaration of Conformity:
The product complies with the
low voltage recommendation 2006/95/EC and the
EMV recommendation 2004/108/EC.
17. Wiring diagram
Type
SM
FC
FM
PD4-M-3C-TRIO (Master)
92740
92745
–
PD4-S (Slave)
92142
92254
92163
LUXOMAT
®
Remote control:
IR-PD4-TRIO-SWI
(incl. wall bracket)
92102
Accessory:
SM-Socket IP44 for 92740
92386
Wire basket BSK for 92740
92467
Wire basket BSK for 92745
92199
Wall bracket for remote control as replacement
92100
15. Article / Part nr. / Accessory
M
A
N
67
14
–
0
50
313
–3
In case the sensing area of the
LUXOMAT
®
PD4-M-
3C-TRIO is too large or areas are being covered that
should not be monitored, the range can be reduced or
limited through use of the enclosed masking clips (e).
14. Exclude sources of interference
13. Range of Coverage
12. Fully / Semi automatic mode
(see DIP switch functions and IR-PD4-TRIO on page 1)
Fully automatic operation
In this operating mode, the lighting switches automati-
cally on and off for increased comfort, depending on
presence and brightness.
- Channel 3 switches on after movement, when one
channel (1 or 2) “detects darkness“
- Channel 3 switches off, when both channels switches
off because of brightness or when the follow-up time
is over.
Semiautomatic operation
In this operating condition, in order to gain increased
savings, the lighting is energized only after being manu-
ally switched on. Switch-off takes place automatically or
manually.
The semiautomatic mode basically behaves like the fully
automatic one. However, the difference is that switching-on
must always be carried out manually!
As many (closer-contact) buttons as desired can be wired
in parallel on the “S” button input (ON/OFF).
20. DIP switch functions
PD4-M-3C-TRIO
2
1
1
2
Walking across
Walking towards
Seated
quer zum Melder gehen
frontal zum Melder gehen
sitzende Tätigkeit
DIP switch
OFF
ON
1 (
A
)
Fully automatic
channel 1, 2 and 3
Semi automatic
channel 1, 2
and 3
2 (
B
)
Power supply ON /
Light ON
Power supply
ON / Light OFF
3 (
C
)
RESET
21. LED function displays
16. Fault-finding
Permanently flashing
Check whether DIP3 switch (RESET) is set to “ON”
Reset to “OFF” if necessary
e
LED Colour Function
Display
6
red Display of movement Flashing:
motion is
detected
5
green Display of light
status channel 1
Flashes twice per second:
- bright enough (Light OFF/
too bright (Light ON)
Flashes once per second:
- power-up delay activated
4
white Semi automatic and
automatic channel 1
Shines in semi-automatic
mode
3
white Semi automatic and
automatic channel 2
Shines in semi-automatic
mode
2
green Display of light
status channel 2
Flashes twice per second:
- bright enough (Light OFF/
too bright (Light ON)
Flashes once per second:
- power-up delay activated
1
red OFF function
Shines, when function is
activated, that means that
light is off in phase of
initialisation
All LED‘s
Confirmation
Flash once per second:
- correct input
flashes twice per second:
- wrong input
flashes 3 times/once per
second:
- Reset in closed mode
flashes twice/once per
second:
- double closed
LED2/LED5 Light measurement
Green LEDs flash by turns:
- light measuring and cal-
culating cut-off threshold
All LED‘s
Status
Flash once per second:
- Detector is double closed.
HA
VA
3
3
DIP
ON
OFF
1 2 3
Standard mode with Master 3-channel TRIO occupancy detectors
L
N
NO
L΄΄΄΄
L
N
C1
N L
R
S
C1/2
NO
R
NO
C2
NO
C3
S
C3
T2
T1
E1
E2
E3
optional
T1&2 = NO button for semi-automatic mode
Slave for enlargement of detection area
18. PD4-M-3C-TRIO – Connections
PD4-M-3C-TRIO-FC
PD4-M-3C-TRIO-SM
L
N
R
Slave
S
C1/2
S
C3
T1 T2
E3
L'
L L
NO
NO
NO
NO
N N
N
R
E2
E1
C3 C3
C2 C2
L
N
R
Slave
R N
T1
E3
E2
E1
NO
C2
NO
C2
L'
C1
L
S
C1/2
NO
C3
NO
C3
T2
S
C3