11. Exclude sources of interference
If the detection zone is too large, or areas are covered that should
not be monitored, use the blinds to reduce or limit those areas.
12. Technical data
Sensor and power supply in one case
Power supply:
110-240 VAC, 50/60 Hz
Power consumption:
ca. 1W
Ambient temperature:
-25°C to +50°C
Degree of protection/class:
IP20 / II
Recommended height
for mounting:
2 - 3 m
Range of coverage Ø
H 2.5 m / T = 18°C:
seated 6.4 m / tangential 24 m /
radial 8 m
Area of coverage:
circular 360°
Dimensions H x Ø [mm]
FC
84.5 x 80 mm
Visible part when built into ceiling:
15 x 80 mm
Lux value:
10 - 2000 Lux
• DALI/DSI
digital BUS control wire, 2-core, no polarity (broadcast only)
Max. no. of series-connected electronic ballasts:
up to 50
Time settings:
1 - 30 min. / test
• Channel 2
Type of contact:
NOC/with pre-travel tungsten
Contact load:
2300 W, cos
ϕ
=1;
1150 VA, cos
ϕ
= 0.5, µ contact
Technical data PD2 Slave
Power supply:
110-240 VAC, 50/60 Hz
Impulse output:
Optocoupler max. 2 W
Impulse duration:
2 sec. or 9 sec.
Dimensions:
see above
Declaration of conformity
This product respects the directives concerning
1. electromagnetic compatibility (2004/108/EU)
2. low voltage (2006/95/EU)
3. restriction of the use of certain hazardous substances in
electrical and electronic equipment (2011/65/EU)
13. Article / Part nr. / Accessory
Type
FC
PD2-Master-DALI/DSI-1C
92486
PD2-Slave
92166
LUXOMAT
®
Remote control:
IR-PD-DALI-1C (incl. wall bracket) 92116
Accessories:
BSK Wire basket
92199
14. LED function indicators
LED function indicators
Process
Standard mode Double locked
Initialisation time
unprogrammed
red flashes
green flashes
Initialisation time
programmed
red flashes
quickly
green flashes
quickly
Motion detection
red flashes on
each detected
movement
green flashes on
each detected
movement
Too bright detected
red flashes 2x
per second
green flashes 2x
per second
Too bright / too dark /
undefined in opened state
red flashes
very quickly
green flashes
very quickly
Toggle DALI/DSI
DSI active
red shines
3 sec.
Toggle DALI/DSI
DALI active
green shines
3 sec.
Toggle HA/VA
VA active
red shines
3 sec.
Toggle HA/VA
VA active
green shines
3 sec.
Toggle Preset/User Preset
active
red shines
3 sec.
Toggle Preset/User User
active
green shines
3 sec.
IR signal valid received
red and white
shines 3 s
IR signal invalid received
red shines
0,5 sec.
100 h function active
red / green
flashes
variable
red / green
flashes
variable
Exit programming mode
If there is no entry
for about 3 min.
the programming
mode is ended
automatically.
Wall bracket for remote control
IR-PD-DALI-1C
IR-PD-DALI-1C
15.
Putting into operation of the remote control
IR-PD-DALI-1C (optional)
Settings with remote control override the potentiometer
and DIP settings.
The DIP settings are reactivated by
• Setting the potentiometers to “TEST“ and ”SUN”, or
• Pressing the “Reset” button on the remote control in open state
Remote control LUXOMAT
®
IR-PD-DALI-1C
1. Check Battery:
Open battery compartment by pressing
the plastic springs together and remov-
ing the battery-holder.
2. Note:
Using the remote control, the occupancy detector can only be
operated in dependence on brightness. The setting "SUN" can
only be set with potentiometer A.
By using the remote control IR-PD-DALI-1C, we recommend to set
potentiometer A on "SUN". Pushing the RESET button (remote
control) would reset the brightness independence of the
occupancy detector (SUN).
!
16. S
ettings by remote control
in open state
Unlocking device
– Activation of the
programming mode
Resetting
when open:
Deletes all
values set with
the remote
control, light
OFF.
Orientation light
on/off
Automatic reading
in the current light
value as new lumi-
nance set value
or
Dimming of the
lighting on the
desired luminance
value
Adjusting of the
luminance set value
from 50 to 1500 Lux
+ / –
small steps
+
/
–
big steps
max
50
Lux
1500
Lux
ON
OFF
max
50
Lux
1500
Lux
ON
OFF
DSI/
DALI
Toggle between DSI
and DALI program
The Factory setting
is DALI
or
+
–
Fully automatic /
semi-automatic mode
Preset/user mode
max
50
Lux
1500
Lux
ON
OFF
Follow-up time
orientation light
at
1
min
10
min
1. Start Light measure-
ment by holding down
the push button
2. Start LED ON/OFF a
short press of pushbutton
optional
optional
optional
optional
Follow-up time
Channel 1: 1 - 30 min.
Follow-up time
Channel 2 (HVAC): 5 -
60 min. or impulse
1
min
5
min
30
min
60
min
Permanent double lock
With this function, the
detector is perma-
nently locked. This
mode can only be
activated during 5 sec.
after closing the detec-
tor. In this mode, only
the function
„Light ON/
OFF“ can be activated.
Red LED flashes
optional
max
50
Lux
1500
Lux
ON
OFF
t < 5 sec.
or