Information – UL Class 1 Division 2 

Nonincendive Field 

Wiring Apparatus

Relationship

Associated Field 

Wiring Apparatus

1

Vmax (or Ui)

>=

Voc (or Vt (or Uo)

2

Imax (or Ii)  

>=

Isc or It (or Lo)

3

Pmax

>=

Po

4

Ci + Ccable  

<=

Ca (or Co)

5

Li + Lcable  

<=

La (or Lo)

The following are UL limitations for the application of customer I/O wiring to 

the indicated B+B products.  These limitations involve the maximum inductance, 

capacitance and resistance that may be connected to I/O lines, current and 

power maximums that can be drawn from the I/O lines, and the maximum output 

voltage from the I/O lines.

Customer I/O wiring is on the left; the B+B product is on the right in the drawing 

below:

Nonincendive Field Wiring Apparatus Control 
Drawing     

(Document # 260-10194-00)

Table 1: Nonincendive Field Wiring Apparatus vs. Associated Field 

Wiring Apparatus per UL Limitations

The following notes are pertinent to Class I, Division 2 applications:

a. Associated apparatus output current must be limited by a resistor such that the output 

voltage-current plot is a straight line drawn between open-circuit voltage and short-circuit 

current.

b. [Optional]   The Nonincendive Field Wiring device does not provide 500 V isolation with 

respect to earth.  Associated apparatus used must be galvanically isolated or dual channel 

shunt zener diode barriers with linear outputs used channel to channel. 

c. Associated apparatus may be in a Division 2 or Zone 2 location if so approved.

d. Selected associated apparatus must be third party listed as providing Nonincendive 

Field Wiring circuits for the application, and have Voc or Vt not exceeding Vmax (or Uo 

not exceeding Ui), Isc or It not exceeding Imax (or Io not exceeding Ii), and the Po of the 

associated apparatus must be less than or equal to the Pmax or Pi of the Nonincendive Field 

Wiring equipment, as shown in Table 1.

e. Capacitance and inductance of the field wiring from the Nonincendive Field Wiring 

equipment to the associated apparatus shall be calculated and must be included in the 

system calculations as shown in Table 1.  Cable capacitance, Ccable, plus Nonincendive 

Field Wiring equipment capacitance, Ci, must be less than the marked capacitance, Ca (or 

Co), shown on any associated apparatus used.  The same applies for inductance (Lcable, Li 

and La or Lo, respectively). Where the cable capacitance and inductance per foot are not 

known, the following values shall be used: Ccable = 60 pF/ft., Lcable = 0.2 µH/ft.

f. Associated apparatus must be installed in accordance with its manufacturer’s control 

drawing and Article 504 of the National Electrical Code (ANSI/NFPA 70) for installation in 

the United States, or Section 18 of the Canadian Electrical Code for installations in Canada.

g. When required by the manufacturer’s control drawing, the associated apparatus must 

be connected to a suitable ground electrode per the National Electrical Code (ANSI/NFPA 

70), the Canadian Electrical Code, or other local installation codes, as applicable.  The 

resistance of the ground path must be less than 1 ohm.

h. Associated apparatus must not be used in combination unless permitted by the associated 

apparatus certification.

i. Control equipment must not use or generate more than 250 V rms or dc with respect to 

earth.

j. The WSB-XMXX and WSD-XMXX are provided with a permanently connected cable 

having the following characteristics:

(Following are some characteristics that should be considered for inclusion.  In general, as 

much information as possible should be included.

Type

Rated Voltage

Rated Current

Maximum Rated Temperature

Conductor size

Insulation type

Insulation thickness

Certifications)

k. Suitability for installation in particular applications is at the discretion of the Authority 

Having Jurisdiction (AHJ).

2.  Nonincendive Field Parameters for DIGITAL OUTPUTS (DO).  Customer’s attached 

equipment (apparatus) cannot exceed each of these values.

Parameter

Value

Definitions – all refer to B+B product DO lines (TB1)

1

Voc

30 Vdc

Maximum output voltage that can be applied by the 

DO lines to customer’s equipment with suitable load 

that limits current (note b)

2

Isc 

100 mA

Maximum output current  that DO lines can supply to 

the customer’s equipment

3

Ca

0.1 uF

Maximum external capacitance that the B+B DO lines 

shall present to customer’s equipment 

4

La

5 mH

Maximum external inductance  that the B+B DO lines 

shall present to customer’s equipment 

5

Po

3.0 w

Maximum output power that DO lines shall supply to 

customer’s equipment 

– note b

b.  Since the Digital Output is an open FET drain, customer will attach a voltage source 

(30 Vdc max) through a load that will limit current to 100 mA maximum.   A typical 

load would thus be R = E/I = 30v/0.1A = 300 ohms.  This load is in series with the FET 

(source-to-drain).  Since the Ron of the FET is 1 ohm max, over 99% of the voltage drop 

will be across the customer load, <1% will be across the FET.  The power dissipated in the 

FET will in this case be P = I**2 x R = (0.1A)**2 x 1 ohm = 10 mW.

3.  Nonincendive Field Parameters for 3.3V REF port.  Customer’s attached equipment 

(apparatus) cannot exceed each of these values.

Parameter

Value

Definitions – all refer to B+B product 3.3V REF (TB1)

1

Vmax

5 VDC

Maximum input voltage that can be applied to the 

3.3V REF line

2

Imax

7 mA

Maximum input current that customer’s equipment 

can draw from the 3.3V REF line.

3

Ci

10.11 uF

Maximum capacitance that customer’s equipment 

shall present to the B+B 3.3V REF line.

4

Li

0 mH

Maximum inductance that customer’s equipment 

shall present to the B+B 3.3V REF line. 

5

Pmax

35 mW

Maximum power that customer’s equipment shall 

draw from 3.3V REF line.

(3.3v x 0.007a)

NOTE 1: 

a.  Suitability for installation in particular applications is at the discretion of the Authority 

Having Jurisdiction (AHJ)

4.    Nonincendive Field Parameters for ANALOG INPUT ports in Voltage-Input mode 

(AI-V).  Customer’s attached equipment (apparatus) cannot exceed each of these values.

Parameter

Value

Definitions – all refer to B+B product AI Ports in 

Voltage mode

1

Vmax

5 VDC

Maximum voltage that can be applied to the AI 

Ports in Voltage mode

2

Imax

1 uA

Maximum input current that customer’s equipment 

can draw from the B+B AI Ports in Voltage mode

3

Ci

0.01 uF

Maximum capacitance that customer’s equipment 

shall present to the B+B AI Ports in Voltage mode

4

Li

0 mH

Maximum inductance that customer’s equipment 

shall present to the B+B AI Ports in Voltage mode

5

Pmax

5 uW

Maximum power that customer’s equipment shall 

draw from B+B AI Ports in Voltage mode

(5v x 1uA)

a.  Suitability for installation in particular applications is at the discretion of the Authority 

Having Jurisdiction (AHJ)

5.    Nonincendive Field Parameters for ANALOG INPUT ports in Current-Loop mode 

(AV-I).  Customer’s attached equipment (apparatus) cannot exceed each of these values.

Parameter

Value

Definitions – all refer to B+B product AI Ports in 

Current-Loop mode

1

Vmax

5 VDC

Maximum voltage that can be applied to the AI Ports 

in Current-Loop mode

2

Imax

20 mA

Maximum input current that customer’s equipment 

can supply to the B+B AI Ports in Current-Loop mode

3

Ci

0 uF

Maximum capacitance that customer’s equipment 

shall present to the B+B AI Ports in Current-Loop 

mode

4

Li

0 mH

Maximum inductance that customer’s equipment 

shall present to the B+B AI Ports in Current-Loop 

mode

5

Pmax

100 mW

Maximum power that customer’s equipment shall 

draw from B&B AI Ports in Current-Loop mode

(5v x 20 mA)

a.  Suitability for installation in particular applications is at the discretion of the Authority 

Having Jurisdiction (AHJ)

a.  Suitability for installation in particular applications is at the discretion of the Authority 

Having Jurisdiction (AHJ)

Table 2: Product DO Lines (TB1)

Table 3: 3.3V REF (TB1)

Table 4: AI Ports in Voltage Mode

Table 5: AI Ports in Current-Loop Mode

Wzzard Intelligent Edge Nodes

1. SUITABLE FOR USE IN CLASS I, 

DIVISION 2, GROUPS A, B, C AND D HAZARDOUS LOCATIONS, OR 

NONHAZARDOUS LOCATIONS ONLY.

2. 

WARNING - EXPLOSION HAZARD

 SUBSTITUTION OF ANY 

COMPONENT MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION 2.

3. 

WARNING - EXPLOSION HAZARD 

DO NOT DISCONNECT 

EQUIPMENT WHILE THE CIRCUIT IS LIVE OR UNLESS THE AREA IS 

KNOWN TO BE FREE OF IGNITABLE CONCENTRATIONS.

4. The unit is to be connected to a Class 2 power source via the terminal 

block.

5. Field wiring conductor minimum insulation rating - 80°C.

6. Use Copper Conductors Only or equivalent.

7. See Instruction Manual for additional information.

Batteries

1. 

Warning

: Risk of Fire and Burns. Do Not Recharge, Open, Crush, Heat 

Above 100°C, or Incinerate the batteries.

2. Batteries are not user replaceable, only a qualified technician should 

replace the batteries.