u 0.0
Setup of the
Lower limit of temperature range
. The minimum difference between lower and upper limit is
20 K
. If you set the
lower limit to a value ≥ upper limit the upper limit will be adjusted to
[lower limit + 20 K]
automatically.
n 500.0
Setup of the
Upper limit of the temperature range
. The minimum difference between upper and lower limit is
20 K
. The upper
limit can only be set to a value = lower limit + 20 K.
[ 0.00
Setup of the
Lower limit of the signal output
. This setting allows an assignment of a certain signal output level to the lower limit
of the temperature range. The adjustment range corresponds to the selected output mode (e.g. 0-5 V).
] 5.00
Setup of the
Upper limit of the signal output
. This setting allows an assignment of a certain signal output level to the upper limit
of the temperature range. The adjustment range corresponds to the selected output mode (e.g. 0-5 V).
U °C
Setup of the
Temperature
unit
[°C or °F].
| 30.0
Setup of the
Lower alarm limit
. This value corresponds to Alarm 1
[►5.6 Alarms]
and is also used as threshold value for relay
1 (if the optional relay board is used).
|| 100.0
Setup of the
Upper alarm limit
. This value corresponds to Alarm 2 [►5.6 Alarms] and is also used as threshold value for relay 2
(if the optional relay board is used).
XHEAD
Setup of the
Ambient temperature compensation
. In dependence on the emissivity value of the object a certain amount of
ambient radiation will be reflected from the object surface. To compensate this impact, this function allows the setup of a fixed
value which represents the ambient radiation.