Azel i-Link SZ-V4 Installation And Operating Instructions Download Page 2

ELECTRONIC THERMOSTATS

 

ALL

  i

-

Link

  controls  are  compatible  with  2,  3  or  4  wire  type 

thermostats.  24VAC  Out  can  be  used  to  supply  power  to  the 
thermostat. For thermostats requiring the 24VAC Common, simply 
connect C terminal from the thermostat to C terminal on the 24VAC 
output. 

Azel  D-135E  thermostat  is  recommended  for  use  with 

i

-

Link 

Controls.

TERMINAL DESCRIPTIONS

Dry Contact Terminals

X   X /End Switch  

Dry Contact End Switch

X1 X1/Zone 1 

 

Zone 1 Dry Contact End Switch

NO COM NC/Zone 1 

Zone 1 Dry Contact End Switch

Line Voltage Terminals

N  

120 VAC Neutral Terminal Input

120 VAC Hot Terminal Input

L    N/CIRC 

120VAC Circulator Power

Low Voltage Terminals

24VAC OUT/R  

24 VAC transformer hot output

24VAC OUT/C 

24 VAC transformer common output

ZONE EXPANSION/1 2 3   ZONE expansion to additional 

  

 

i

-Link 

zone valve controls

THERMOSTATS

R/T1 

Zone 1 24VAC Thermostat Hot Terminal 

W/T1 

Zone 1 Thermostat Switching Terminal

R/T2 

Zone 2 24VAC Thermostat Hot Terminal 

W/T2 

Zone 2 Thermostat Switching Terminal 

R/T3 

Zone 3 24VAC Thermostat Hot Terminal 

W/T3 

Zone 3 Thermostat Switching Terminal 

R/T4 

Zone 4 24VAC Thermostat Hot Terminal 

W/T4 

Zone 4 Thermostat Switching Terminal 

R/T5 

Zone 5 24VAC Thermostat Hot Terminal 

W/T5 

Zone 5 Thermostat Switching Terminal 

R/T6 

Zone 6 24VAC Thermostat Hot Terminal 

W/T6 

Zone 6 Thermostat Switching Terminal  

ZONE VALVES (ZONE 1 - 6)

1  2 

Terminals for zone valve motor connections

3  4  

Terminals for zone valve end switch connections

NOTE ON WIRING INSTRUCTIONS

 

SZ-V6 units are used as examples on the wiring diagrams. SZ-V4 
units can be wired in the same manner. 
If Azel  D-135E  digital  thermostat  is  used,  it  can  be  powered  by 
connecting terminal 4 & 5 of D-135E to 24VAC Out (R & C) of i-Link 
controls. For simplicity, this connection is not shown in all example.

  

i

-Link ZONE EXPANSION

i

-Link zone valve 

controller can be expanded to unlimited number of 

zones with additional 

i

-Link

 zone valve controllers. Simply connect 

terminals “1 2 3 ” of the “Master” unit to terminals “1 2 3 ” of the “Slave” 
unit with 18AWG wires. More units can be connected in the similar 
manner. Use the Master/Slave Switch to define the unit as “Master” or 
“Slave”. The priority zone of the “Master” unit (if zone 1 priority switch is 
set to 

ON or Timer) 

will turn off all other zones of the “Slave” units. 

After expansion, all the units will act as a single unit. This means only 
one set of X-X(End Switch) terminal is needed to connect to the “TT” 
on the boiler control. Also, only one circulator connection is needed. 
Factory default setting  “Master”.  

 

Note: It is important to set the slide switch before turning on the power.

L.E.D. SYSTEM STATUS INDICATION LIGHTS

 

YELLOW   light (T1-T6) indicates that the thermostat is calling for 
heat and the corresponding zone valve is energized. 

RED light (Z1-Z6) indicates zone valve (with an end switch) is fully 
opened and End Switch (X-X) is closed. In case of two wire type 
zone valve, the zone valve is energized. If the 3-minute XX delay 
timer is set to OFF, End Switch is closed.  If the XX  delay timer is set 
to ON, End Switch is closed three minutes after thermostat calls for 
heat. 

GREEN Power light indicates presence of power supply.

GREEN solid Priority Timer light indicates that the one-hour timer is 
started.     GREEN flashing light indicates one hour priority timer is 
expired  and  all  heating  zones  are  released  from  locking  out. All 
zones can operate independently.

TWO WIRE TYPE ZONE VALVE

 

When two wire type zone valve is used, JUMPER 3&4 DIP switch 
can be set to ON for each corresponding zone so that  there is no 
need to put a wire jumper across terminal R-R. Also, XX (End 
Switch)  Delay Timer  can  be  set  to  ON. This  allows  a  delay  of 
three minutes on closing the X-X End Switches after thermostat 
calls for heat which gives sufficient time for zone valve to fully 
open.

TROUBLE SHOOTING

When 120VAC is supplied to 

i

-Link 

controllers, the green 

power light should be on. 

!

If  the thermostat is closed and yellow zone light is on, the 
power should be supplied to the zone valve. If the zone 
valve is not actuated or if the zone valve end switch is not 
closed (red light is not turning on), check the zone valve 
for functionality.

!

If yellow zone (1-6) light is on all the time

, check the 

thermostat for functionality. Remove the thermostat from 
the 

i

-Link 

controller and put a piece of wire across R/T 

and W/T terminal to simulate the thermostat calling for 
heat. If everything works properly, then the thermostat is 
faulty. 

!

I

f the green power light is off

, check the fuse and the 

presence of 120VAC power supply. If the fuse is fine and 
there  is  no  power  output  on  R  C  terminals  of  24VAC 
OUTPUTS, the transformer(model: 5011F) needs to be 
replaced.  