background image

5

AB-6601

 

z

Cautions for installing this product

• 

Install this product in a location where representative 
temperature of the measuring object can be measured.

• 

Do not install the product in locations such as the 
following. Temperature may not be correctly measured.  

 Where exposed to warm or cold wind directly.

  

  Where air stagnates or there is a draft. 

  

• 

Where the product cannot be mounted firmly. 

 

• 

Where unauthorized persons can have easy access.

• 

Secure space around the product for maintenance.

 

z

Installation procedure (Model TY6300Z1000)

IMPORTANT

• 

Do not leave the cover for the unit and 
terminals detached.

• 

During installation, do not twist, deform, 
flatten, or damage the temperature 
sensing element.

• 

Remove the knockout holes being careful 
not to leave protrusions or burrs.    
Failure to do so might damage the wires 
or cause injury.

(1) Loosen the cover mounting screw and remove 

the cover.

(2) Loosen the terminal cover screw and remove 

the terminal cover.

(3) Remove the knockout hole at the side where the 

wires are pulled in.

Note:Knockout hole is removed by simply pushing it from the 

inside.

(4) Remove the protrusions or burrs at the opening. 
(5) Attach the conduit. 

 

Wiring conduit is commercially available.

(6) With the wood screws, mount and fix the case 

on a wall at an appropriate height.

Note:Be careful not to distort the temperature sensing ele-

ment (coiled).

(7) Connect wires.

Refer to ■ 

Wiring.

(8) Attach and fix the terminal cover to the original 

position with the mounting screw.

(9) Attach and fix the cover with the cover mounting 

screw.

 

z

Attaching the grommet (accessory part)

Figure 2.  Grommet (mm)

If the left-side knockout hole is used and a conduit 
is not used, attach the included grommet to the 
openings as shown in Figure 3.
The grommet prevents a finger from entering into 
the opening in order not to cause electric shock.

Note:Before wiring, attach the grommet.

(1) Insert the grommet in the knockout hole as 

illustrated in Figure 4.

(2) Push the grommet until the tab clicks.

(3) Ensure the grommet is firmly inserted.

Note:Do wirings through the grommet following the instructions 

in this manual.

Figure 3.  Knockout hole for attaching the grommet

Figure 4.  Attaching the grommet

φ23.8

6.4

Tab

(on both sides)

Knockout hole

(left side)

Grommet

Note:Insert the small diameter 

side of the grommet into 

the knockout hole.

Summary of Contents for TY6300Z1000

Page 1: ...vestock crib or the like for farm or horticultural applications Also it can be used as anti freeze thermostat for ON OFF operation of a circulating pump or a heater or as a high low limit switch Featu...

Page 2: ...locations such as the following Temperature may not be correctly measured Where exposed to warm or cold wind directly Where air stagnates or there is a draft Where the product cannot be securely mount...

Page 3: ...e Firmly tighten the terminal screws Insufficient tightening of the terminal screws might cause overheating or fire Do not disassemble the product Doing so might cause electric shock or device failure...

Page 4: ...rommets Failure to do so might cause electric shock due to touching the terminals CAUTION Use this product under the operating conditions for temperature humidity power vibration shock mounting direct...

Page 5: ...y simply pushing it from the inside 4 Remove the protrusions or burrs at the opening 5 Attach the conduit Wiring conduit is commercially available 6 With the wood screws mount and fix the case on a wa...

Page 6: ...Main unit Figure 6 Attaching detaching the terminal cover Terminal cover Terminal cover mounting screw x1 Main unit Figure 7 Figure 8 103 128 8 128 8 Wall or panel Hole 73 2 73 2 11 9 103 11 9 Main u...

Page 7: ...onduit is commercially available Note Attach the grommet as necessary referring to Attaching the grommet accessory part 6 Attach the product and the adapter plate through the two holes located upper t...

Page 8: ...sions according to each model referring to this figure Figure 11 Mounting the product replacing Model T631A1121 1 Main unit Jointly screw on wall Flat head screws 2 pcs M3 L 5 Adapter plate sold separ...

Page 9: ...he instructions described in this manual and the manuals for other devices connected to this product In the final step connect the power supply to the product If you touch the terminals mistakenly an...

Page 10: ...d crimping terminal M4 size for wiring When the product is grounded outside the case Do wiring as illustrated in Figure 13 a When the product is grounded inside the case Referring to Figure 13 b faste...

Page 11: ...wer supply Model TY6300Z1000 Model TY6300Z1000 Model TY6300Z1000 Ventilation fan Hot water boiler Electromagnetic valve Power supply Figure 17 Controlling warm air heater Figure 18 Controlling chiller...

Page 12: ...icator needle at the desired temperature setpoint Turn the setting knob clockwise to raise the temperature setting or counterclockwise to lower it Figure 20 Temperature setting z z Switching operation...

Page 13: ...ectric shock CAUTION Do not disassemble the product Doing so might cause electric shock or device failure Determine the appropriate cycle of maintenance and inspection taking into consideration the en...

Page 14: ...14 AB 6601 This blank page is added for page layout purposes...

Page 15: ...15 AB 6601 This blank page is added for page layout purposes...

Page 16: ...16 Rev 2 0 Aug 2015 AB 6601 J AI 6601 Rev 3 0 http www azbil com Building Systems Company Specifications are subject to change without notice...