33
Chapter 5. APPLICATION OPERATION
Parameter setup item list
No.
Item
displayed
Item
Description
Factory
Setting
Setting
Range
Remarks
1
A. HI
(*
1
) Instantaneous flow
rate upper limit alarm
(Upper limit of
measurement
range) m
3
/h
(normal)
(0 to 400% of measure-
ment upper limit) m
3
/h
(normal)
Selection of an alarm
detection condition is
required in function
setup
C-02
.
2
A. H. HY
Hysteresis for instanta-
neous flow rate upper
limit alarm
(Within 2% of
measurement
upper limit)
m
3
/h (normal)
(0 to 200% of measure-
ment upper limit) m
3
/h
(normal)
3
A. LO
*
2
Instantaneous flow
rate lower limit alarm
(Lower limit of
measure range)
m
3
/h (normal)
(0 to 200% of measure-
ment upper limit) m
3
/h
(normal)
4
A. L. HY
Hysteresis for instanta-
neous flow rate lower
limit alarm
(Within 2% of
measurement
upper limit)
m
3
/h(normal)
(0 to 200% of measure-
ment upper limit) m
3
/h
(normal)
5
A. dLY
Delay timing for
instantaneous flow
rate alarm judgment
60.0s
0.0 to 999.9s
6
E. SP. L
Integration event
setup (lower four
digits)
0m
3
0 to
99,999,999m
3
Value set is valid only
when selecting integra-
tion event output in
either
C-03
or
C-04
of function setup.
7
E. SP. H
Integration event
setup (upper four
digits)
8
E. C. dL
Integration reset delay
time
10.0s
0.0 to 999.9s
Value set is valid only
when selecting auto-
matic reset by integra-
tion reset delay in C-06
of function setup.
9
bIAS
Instantaneous flow
rate bias (PV bias)
0m
3
/h
(-20 to +20% of mea-
surement upper limit)
m
3
/h (normal)
10
Out. H
Instantaneous flow
rate output 5V (20mA)
scaling
(Upper limit of
measurement
range)m
3
/h
(normal)
(0 to 400% of measure-
ment upper limit) m
3
/h
(normal)
11
Out. L
Instantaneous flow
rate output 1V (4mA)
scaling
0m
3
/h
(0 to 200% of measure-
ment upper limit) m
3
/h
(normal)
12
GAS. C
Gas composition com-
pensation coefficient
1.000
0.100 to 4.000
If a model for fuel gas
(13A-46MJ/m
3
) is used
for 13A-45MJ/m
3
gas,
change the value to
1.029.