20
Chapter 3. MOUNTING AND WIRING
z
Wiring the 24Vdc power supply model
The following shows wiring of the 24Vdc power supply model and
connection names:
Load
Load
1 to 5V or 4 to 20mA output
Open collector output
(4 to 20mA output model only)
*
+
−
Internal circuit
CN1
Terminal 2: COM
Terminal 1: 24Vdc
Terminal 3: OUTPUT
Terminal 4: EVENT2
Terminal 5: RELAY
Terminal 6: RELAY
Relay output
(+)
*: A DC power supply can also be
used for the load that is wired to
terminals 5 and 6.
Terminal No.
Connection Name
Description
1
24Vdc
Power supply
2
COM
Common
3
OUTPUT
Analog output (+)
4
EVENT2
Event output 2 NPN open collector, integrated pulse
5
RELAY
Event output 1 contact output (relay output)
6
RELAY
Event output 1 contact output (relay output)