Azbil HTY78 Specifications & Instructions Download Page 10

AB-5961 

10 

Wiring 

 WARNING  

 

Before wiring and maintenance, be sure to turn off the power to the product. 
Failure to do so might cause electric shock. 

 

After wiring, be sure to reattach the terminal cover.  
Failure to do so might cause electric shock. 

 

 CAUTION 

 

Installation and wiring must be performed by qualified personnel in accordance with all applicable safety standards.

 

All wiring must comply with applicable codes and ordinances. 

 

Be sure to provide a circuit breaker for the power to the product. 

 

To connect the wires to the screw terminals, use crimp terminal lugs with insulation.  
Failure to do so might cause fire or device failure due to short circuit. 

 

Firmly tighten the terminal screws.   
Insufficient tightening of the terminal screws might cause fire or overheating. 

 

Do not use unused/spare terminals on the product as relay terminals. 
Doing so might cause malfunction. 

 

Precautions for wiring 

  For power wiring and temperature/humidity output wiring, 1.25 mm² or 2 mm² shielded multi-core cables (JCS CVV-S 

cables) are recommended.   

 

-  Be sure to ground the shielding on the controller side. 

 

-  For Model HTY78X3D/HY78X3D/TY78X3D series, ground the shielding on the duct sensor side as well. 

 

-  If dust-proof and splash-proof enclosure are not required, 
  1.25 mm² or 2 mm² JIS IV cable can be used for power wiring and temperature output wiring, and 1.25 mm² shielded 
  cable can be used for humidity output wiring. 

 

-  The maximum wiring length is 100 m. 

 

JCS: Japanese Electric Wire & Cable Makers’ Association Standards

 

  Do not connect the cable for power supply to the temperature output terminals. 

Doing so will generate smoke. 

  Always check wiring before supplying power. 

Do not allow the 24 V AC transformer for the duct sensor to supply the power to any other devices. 

  Because the temperature sensor model with RTD (Pt1000) output is two-wire, the wire resistance will cause measuring 

error.  For instance, 1.25 mm

2

 size wire causes approx. 0.1 °C measuring error every 10 m.  Correct the measuring error by 

setting the controller in connection. 

 

Summary of Contents for HTY78

Page 1: ...ioning ducts and AHU and meteorological observation as well as industrial applications Model TY78X3 series temperature sensor and Model HY78X3 series humidity sensor are also available AHU Air handlin...

Page 2: ...the left indicates general instructions WARNING Before wiring and maintenance be sure to turn off the power to the product Failure to do so might cause electric shock After wiring be sure to reattach...

Page 3: ...t Doing so might cause device failure Dispose of this product as industrial waste in accordance with your local regulations Do not reuse all or a part of this product IMPORTANT Measuring accuracy of t...

Page 4: ...0 Short probe No power N A RTD Pt100 TY7803Z0K00 Long probe TY7813Z0K00 Short probe No power N A RTD Pt1000 HTY7803D4400 Long probe HTY7813D4400 Short probe 24 V DC two wire 4 20 mA DC 4 20 mA DC HY78...

Page 5: ...TY78X3D series Time constant at 2 m s air velocity Humidity 1 min or less at constant temperature 24 V AC 10 15 50 Hz 60 Hz 24 V DC 10 for Models HTY78X3T series HY78X3T series Power supply 24 V DC 1...

Page 6: ...hort probe type Installation onto an duct or AHU in an instrument shelter with the dedicated bracket Wiring length Max 100 m Connection Terminal block connection AHU Air handling unit IEC Internationa...

Page 7: ...3 HY7803 mm Models HTY7813 TY7813 HY7813 series Figure 2 Dimensions Models HTY7813 TY7813 HY7813 mm Mounting bracket Part No 83157235 001 optional Figure 3 Dimensions Part No 83157235 001 mm 30 25 50...

Page 8: ...ceed the probe limit operating condition AHU Air handling unit Do not allow condensation especially when installing the probe pointing upward Condensation water that remains in the filter cap slits mi...

Page 9: ...ing bracket onto the duct so that the shorter cylindrical part overhangs from the mounting surface Fasten the mounting bracket with accessory M4 screws Figure 10 Mounting bracket on the panel 3 Releas...

Page 10: ...wiring and temperature humidity output wiring 1 25 mm or 2 mm shielded multi core cables JCS CVV S cables are recommended Be sure to ground the shielding on the controller side For Model HTY78X3D HY78...

Page 11: ...r insufficient removal ratio provide an isolator on the controller input wiring Note No problem will occur for connecting the duct humidity sensor or duct temperature humidity sensor to our controller...

Page 12: ...er of the conductors Temporarily screw the conduit connector and the attachment and select an O ring appropriate for the cable Figure 18 Conduit connection 1 2 Lead the cable into the duct sensor thro...

Page 13: ...power Models HTY7803T1P00 HTY7803T4P00 HTY7813T1P00 HTY7813T4P00 7 conductors Figure 23 Terminal wiring Duct humidity sensor with 1 5 V 4 20mA humidity output 24 V AC DC power Models HY7803T1000 HY780...

Page 14: ...oose wiring Tighten the terminals Disconnected wiring Re perform wiring Power supply voltage No output Unstable output Duct sensor main unit damages Replace the duct sensor Slow response to output Moi...

Page 15: ...y use a slotted screwdriver or other tools while replacing the filter Failure to do so might damage the electronic components and rubber packing 3 Attach the new filter and then the new filter cap to...

Page 16: ...liable calibration instrument for the single point calibration Carefully handle the duct sensor and check the appropriate environment for the calibration Calibrated digital multimeter is recommended t...

Reviews: