8-12
Chapter 8. PROGRAM SETUP
●
●
When event type is PV type event
(1) In the setting display state, move to the event 1 to 5 items of the
segment to be set up on the programming map.
(2) If you press
ENT
, the upper display starts blinking to indicate
start of entry to the No.1 setup.
(3) Press
,
,
or
to set to the No.1 setup event
operating point setting.
Setting range: -1999 to +9999 U
0 to 9999 U (in case of absolute value deviation
event)
-10.0 to +110.0% (in case of MV, MFB event)
(4) When you press
ENT
, blinking on the upper display stops.
(When
FUNC
+
CLR
are pressed, the upper display returns to
“- - - -” and stops blinking.)
●
●
Display (PV type event)
• “- - - -” is displayed for the setting values in non-set segments.
• When setup data
C
6
8
is set to 1, event 1 to 5 items on the pro-
gramming map are skipped and not displayed.
●
●
When event type is a controller event
The event item on the programming map is skipped and not dis-
played.
Upper display
Program No. Segment No.
Pattern
tendency
LEDs corresponding to T1 to T5 lit.