Azbil C35 Quick Reference Manual Download Page 5

5

For step numbers indicated in red like 

5

 , the following precaution applies:

• 

If the key lock is set, the numerical value does not flash, and the value cannot be changed. 
To change a numerical value, cancel the key lock first.

AUTO/MANUAL

 mode selection

1

Press [display] once 
to get the operation 
display.

The [mode] key can be 
used for 1 of 7 different 
operations. 
The initial (factory) set-
ting is "AUTO/MANUAL 
selection".

2

Press and hold [mode] 
for more than 2s, 

Man

 

flashes on the lower 
display.

If the control method is 
set to "ON/OFF control" 
and if the DI assignment 
is "AUTO/MANUAL," the 
display does not blink 
and the setting cannot be 
changed.

3

When 

Man

 appears, 

stop pressing [mode]. 
The MV is shown on 
the lower display. 
The rightmost digit of 
the MV on the lower 
display flashes and its 
value can be changed.

4

Press [<], [ ] or [ ] to 
change to the desired 
MV value. 
Even while the num-
ber is flashing, the MV 
is changed at the same 
time that the number 
is changed.

For the flashing MV in step 3, either bumpless transition (the same 
value as before the change) or preset MANUAL value (the value set 
in setup 

C20

) can be selected (in setup 

C19

, Output operation at 

changing Auto/Manual).

Execution of 

position proportional control auto adjust

When control output is R1 (motor relay output) and setup 

C57

 is "0" 

(initial value) or "1", the following position proportional control auto 
adjust is necessary.

1

Press [display] once 
to get the operation 
display.

2

Press and hold [para] 
for more than 2s to get 
the parameter setup 
display. 

MOde

 flashes 

on the upper display.

3

Press [ ] or [ ] repeat-
edly until 

StUP

 is 

flashing on the upper 
display.

4

Press [enter] to get 

C0

 

1

 on the upper 

display. 
Press [<], [ ] or [ ] to 
change to 

C60

(

C60

: motor adjust)

5

If [enter] is pressed, the 
lower display flashes. 
Press [ ] or [ ] to  get 

1

Press [enter] and auto 
adjustment starts.

6

CA.CL

 is displayed on 

the upper display and 
open contact is ON. 
The lower display 
shows the MFB count 
value and when count 
is stable, 

CA.OP

 is dis-

played on the upper 
diplay and closed con-
tact is ON. 
When the count value 
is stable, auto adjust 
completes to get op-
eration display.

After starting auto adjust, press [display] key to stop auto adjust.
During auto adjust the key operation except [display] key of stop-
ping auto adjust is impossible.

Setup of

 event value

In this example, the event set value and hysteresis for the event 1 
operation type is set to deviation high limit.

1

Press [display] once 
to get the operation 
display.

2

Press and hold [para] 
for more than 2s to get 
the parameter setup 
display. 

MOde

 flashes 

on the upper display.

3

Press [ ] twice or [ ]  
repeatedly, and 

EV

 

flashes on the upper 
display.

4

Press [enter] to get 

e

 

1

 

on the upper display 
and 

0

 is displayed on 

the lower display.

0

 on the lower display indi-

cates that the event main 
setting is "0".

5

If [enter] is pressed, 
the rightmost digit 
on the lower display 
flashes, and can be 
changed. 
Press [<], [ ] or [ ], and 
change to the desired 
value for event set 
value. In this case, the 
flashing of the numeri-
cal value implies that it 
is not yet set.

6

If [enter] is pressed, 
the changed numeri-
cal value is set and 
changes from flashing 
to continuously lit.

Similarly, use 

e2

 to set a value for event 2, and 

e3

 to set a value 

for event 3.

7

To continue from this 
point and set hyster-
esis as well, press [ ] 
twice or [ ] repeatedly 
to get 

E

 

1.HY

 on the 

upper display. The 
lower display says 5.

5

 on the lower display 

indicates that the event 
hysteresis is "5".

8

In the same way that 
event settings were 
changed, press [enter] 
to make the number 
flash, and then press 
[<], [ ] or [ ] to change 
to the desired setting 
for hysteresis. After 
that, press [enter] to 
finalize the setting.

Similarly, use 

E2.HY

 to set a value for event 2, and 

E3.HY

 to set a 

value for event 3.

Memo

Summary of Contents for C35

Page 1: ...en left and right it performs MV graph DI monitor internal event monitor and other display functions Mode indicators man Lights when MANUAL AUTO mode if not lit rsp Lights when RSP LSP mode if not lit ev1 ev2 ev3 Lights when event relays are ON ot1 ot2 Lights when the control output is ON always lit when the current output is used mode key When this key is pressed and held for more than 1 second i...

Page 2: ... No Step remaining time PV value MV value Timer remaining time 3 Internal event 3 delay time Internal event 3 sub setting Setting value Internal event 3 main setting Setting value SP Event PID Parameter Extendedtuning 2 second press hold of para key display key 3 Mode 2 second press hold of para key para key or key enter key key While AUtO is flashing enter key While MAn is flashing enter key to 1...

Page 3: ...b setting Setting value Internal event 2 main setting Setting value Timer remaining time 1 Internal event 1 delay time Internal event 1 sub setting Setting value Internal event 1 main setting Setting value Coolmanipulated variable MV value MFB MFB value Setup Lock key enter key Instrumentinformation 2 second press hold of para key Event configuration DIassignment DO assignment User function para k...

Page 4: ...ulate PID values Check that this operation does not create any problems for the as sociated equipment before executing AT 1 Press display once to get the operation display 2 Press and hold para for more than 2s to get the parameter setup display MOde flashes on the upper display 3 Press enter or to get A M on the upper display and autO on the lower display If the control method is ON OFF control a...

Page 5: ... Press or to get 1 Press enter and auto adjustment starts 6 CA CL is displayed on the upper display and open contact is ON The lower display shows the MFB count value and when count is stable CA OP is dis played on the upper diplay and closed con tact is ON When the count value is stable auto adjust completes to get op eration display After starting auto adjust press display key to stop auto adjus...

Page 6: ...D Conventional PID 1 Ra PID High performance PID 0 JF Ov Just FiTTER assistance coefficient 0 to 100 0 1 Normal Standard control characteristics Immediate response Control characteristics that respond immediately to external disturbance Stable Control characteristics having less up down fluctuation of PV ZOne Zone bank Display Item Contents Initial value Settingvalue ZO 1 to ZO 7 Zone 1 to 7 1999 ...

Page 7: ...ication DI1 to 4 22 MANUAL 23 READY 24 RSP 25 AT running 26 During SP ramp 27 Undefined 28 Alarm occurs 29 PV alarm occurs 30 Undefined 31 mode key pressing status 32 Event output 1 status 33 Control output 1 status 2 to 5 or 0 dI 1 4 to dI 5 4 Internal contact 1 to 5 Input assignment B 0 dI 1 5 to dI 5 5 Internal contact 1 to 5 Input assignment C 0 dI 1 6 to dI 5 6 Internal contact 1 to 5 Input a...

Page 8: ... or 2 or both A current exceeding the upper limit of the display range was measured The number of CT turns or the number of CT power wire loops is incorrectly set or wiring is incorrect Use a CT with the cor rect number of turns for the display range Reset the number of CT turns Reset the number of CT power wire loops Check the wiring Unit failure AL70 A D conversion failure A D converter is fault...