77
Transducer Block “Sensor 1 and 2”
Parameter
Write access
with operating
mode
(MODE_BLK)
Description
Polynom (Nickel/
Copper) Measuring
Range Maximum
(POLY_COEFF_MAX)
AUTO - OOS
Upper calculation limit for the RTD polynom (nickel/
copper) linearization.
Polynom (Nickel/
Copper) Measuring
Range Minimum
(POLY_COEFF_MIN)
AUTO - OOS
Lower calculation limit for the RTD polynom (nickel/
copper) linearization.
Reference junction
(RJ_VALUE)
AUTO - OOS
Internal reference temperature measurement:
VALUE
STATUS
Reference junction
type
(RJ_TYPE)
AUTO - OOS
Configuration of reference junction measurement for
temperature compensation:
NO_REFERENCE: No temperature compensation
is used.
INTERNAL: Internal reference junction
temperature is used for the temperature
compensation.
EXTERNAL: RJ_EXTERNAL_VALUE is used for
the temperature compensation.
Reference junction
value unit
(RJ_UNIT)
Read only
Unit of the internal reference temperature. This
always corresponds to the unit set in SENSOR_
RANGE --> UNITS_INDEX.
Reference junction
external value
(RJ_EXTERNAL_
VALUE)
AUTO - OOS
Value for temperature compensation (see RJ_TYPE
parameter).
Reference junction
max. indicator
(RJ_MAX_
INDICATOR)
Read only
Max. indicator of the internal reference temperature
is stored in the nonvolatile memory in intervals of 10
minutes.
Reference junction
min. indicator
(RJ_MIN_
INDICATOR)
Read only
Min. indicator of the internal reference temperature
is stored in the nonvolatile memory in intervals of 10
minutes.