![Axpert KING 3KVA Service Manual Download Page 12](http://html1.mh-extra.com/html/axpert/king-3kva/king-3kva_service-manual_3041279012.webp)
SERVICE MANUAL
3KVA/5KVA-230V
12
V201703A
Q46
Q47
Q49
Q48
The Q46and Q48 are 11-300012-00G (TR 2A 50V NPN TO-92)
The Q47and Q49 are 11-300005-00G (TR 2A 50V PNP TO-92NL)
Q15
Q41
Q16
Q43
The Q41 and Q43 are 11-300012-00G (TR 2A 50V NPN TO-92)
The Q15 and Q16 are 11-300005-00G (TR 2A 50V PNP TO-92NL)
Parts
Attribute
Reference values
Failure status
Q46/Q48/Q41/Q43
Resistor
BE: 434.2k
BC: 429.3k
CE: 19.52k
Short or explosion