UMAX180800, 20 Thermocouple, 2 RTD, 4 Inputs, 6 Relays Dual CAN Controller
Version 1
Page: 11-71
FMI=4, Voltage Below Normal, Or
Shorted To Low Source
FMI=3, Voltage Above Normal, Or Shorted To
High Source
FMI=5, Current Below Normal Or Open
Circuit
FMI=6, Current Above Normal Or Grounded
Circuit
FMI=17, Data Valid But Below Normal
Operating Range
FMI=15, Data Valid But Above Normal
Operating Range
FMI=18, Data Valid But Below Normal
Operating Range
FMI=16, Data Valid But Above Normal
Operating Range
timer for the Diagnostic function block. If the fault has remained
2.5.1 Network Bus Terminating Resistors
The controller does not have an embedded 120 Ohm CAN bus terminating resistor.
Terminating resistors should be installed externally on both ends of the CAN twisted pair cable
according to the J1939/11(15) standards to avoid communication errors.
Even if the length of the CAN network is short and the signal reflection from both ends of the
cable can be ignored, at least one 120 Ohm resistor is required for the majority of CAN
transceivers to operate properly.
2.6 Modbus TCP Interface
The Modbus TCP/IP interface
1
runs over a standard 10/100 Mbit/s Ethernet link. The controller
is presented as a slave device (a server) on the Modbus network. It supports with up to 8
simultaneous client connections from master devices.
1
The interface is compliant with: