Water Leak Detector - Four Zone with open/short-circuit detection

Page 3 of 3

Sensitivity

Within 30 seconds of applying power to the AX-WLDF, with the cable connected, adjust the sensitivity potentiometers
on each input by turning clockwise (increasing sensitivity) until the zone LED illuminates red, and then anti-clockwise
(reducing sensitivity) until the zone LED goes off. Less sensitivity may be needed when long runs of cable are used. If
the input is not used it should be disabled, see Disable zone.

Testing

To test the installation, after the sensitivity has been set, put a wet cloth over the cable to simulate a water leak, the
indicator zone LED will illuminate solid red. Remove the cloth, short across the mute input, and if the cable is dry the
zone LED will be solid green.

Audible alarm output

If  the unit is in alarm and there is no mute switch in use, the alarm can be silenced by shorting across the mute terminals.
If the audible alarm is not required the mute terminals can be permanently shorted.

Alarm relay outputs and alarm LED

Only when the fault is removed and the mute contacts closed will the alarm relay contacts return to normal, and the
Alarm LED extinguish.

Cable fault

The unit monitors the cable for open and short circuit conditions. Only 1 cable or sensor should be connected to each
zone  input.  Connecting  two  cables  or  sensor  to  one  zone  input  will  interfere  with  the  cable  fault  detection  and  unit
sensitivity.  When a fault is detected the the Zone relay and General relay will go into the alarm state, the 0-10V will
show an alarm for the zone and the zone LED will flash red.

Analogue 0-10V output:

The  table  below  indicates  the  output  voltage  for  each  fault  condition  (Alarm  =  water  detected,  open  circuit  or  short
circuit) (OK = No alarm or input disabled):

Channel 1

Channel 2

Channel 3

Channel 4

Analogue Output

OK

OK

OK

OK

10.00V

ALARM

OK

OK

OK

9.33V

OK

ALARM

OK

OK

8.67V

ALARM

ALARM

OK

OK

8.00V

OK

OK

ALARM

OK

7.33V

ALARM

OK

ALARM

OK

6.67V

OK

ALARM

ALARM

OK

6.00V

ALARM

ALARM

ALARM

OK

5.33V

OK

OK

OK

ALARM

4.67V

ALARM

OK

OK

ALARM

4.00V

OK

ALARM

OK

ALARM

3.33V

ALARM

ALARM

OK

ALARM

2.67V

OK

OK

ALARM

ALARM

2.00V

ALARM

OK

ALARM

ALARM

1.33V

OK

ALARM

ALARM

ALARM

0.67V

ALARM

ALARM

ALARM

ALARM

0V