Axio AX-ET-6 Quick Start Manual Download Page 2

AX-ET-6

Electronic Thermostat – Six stage

Installation

The AX-ET-6 should be installed by a suitably qualified technician in conjunction with any guidelines for the equipment it is to be 
connected to. Field wiring should be installed to satisfy the requirements set out by the manufacturer of the equipment that the module 
is being connected to.

Description and Connections

 2 of 4

Menu

Repeatedly press  

 to scroll through the Actual, Min-max, 

Setpoint, On Delay and Off Delay displays.

Setpoint

The setpoint can be adjusted between -10

°

C and 110

°

C using the 

 and 

 switches. When connected a remote pot can 

be used to adjust the setpoint value by either ±4

°

C or ±20

°

C from 

the value set. All the stage offsets are fixed to the setpoint and 
track changes in the setpoint value. It is possible to provide the 
same switching actions with different setpoint and offset 
combinations. The only limitation on the setpoint location is that 
all cooling offsets are above the setpoint and all heating offsets 
are below the setpoint.

Setpoint adjustment

When the Actual temperature display is visible press 

 or 

 to select the Setpoint display then press 

 or 

 to adjust the setpoint. 

Stage offset

The stage offset sets the centre point of the heating or cooling 
stage. If the stage is set for heating the offset is taken away from 
the setpoint. If the stage is set for cooling the offset is added to 
the setpoint.

Stage differential

This sets the total differential for the stage. The differential is 
centred on the stage offset, therefore a differential of 4

°

C will set 

the stage relay switching points to 2

°

C above the offset and 2

°

below the offset.

MENU

I NC

DEC

I NC

DEC

I NC

DEC

Stage switching

If the stage is set for cooling the relay will switch on when the 
temperature rises above the upper switching point and will 
switch off when the temperature falls below the lower switching 
point. If the stage is set for heating the relay will switch on when 
the temperature falls below the lower switching point and will 
switch off when the temperature rises above the upper switching 
point. An example of these values is given on the next page.

Setback

To activate the setback close the contact across the setback 
terminals, the display will show Actual 

S

b

. When Setback is 

active it will increase all the offsets by the set amount. This will 
reduce the heating stage switching points and increase the 
cooling stage switching points.

Remote Setpoint (External potentiometer)

Select the required range, ±4

°

C, ±20

°

C using the set-up mode and 

connect a  1-11kΩ potentiometer across the External Pot 
terminals. The setpoint display will show SP with EP and will 
show the adjusted setpoint value.

Minimum and maximum temperature

The minimum and maximum sensor temperature values are 
stored by the AX-ET-6 until power is removed. When the Actual 
temperature display is visible press 

 to display the Min 

Max Output display. Press 

 to display the minimum 

value. Press 

 to toggle between the minimum and 

maximum values. Hold 

 down for 2 seconds to reset the 

minimum and maximum values.

MENU

I NC

I NC

I NC

MENU

0V Common

 

24Vac/dc

Stage 

1

Sensor External

Pot

Set

Back

AX-ET6-24

Actual

25.0°C

DEC

INC

Stage 

2

Stage 

3

Stage 

4

230Vac

L     N

Stage 

5

Stage 

6

MENU

Stage 

1

Sensor External

Pot

Set

Back

AX-ET6

-230

Actual

25.0°C

DEC

INC

Stage 

2

Stage 

3

Stage 

4

Stage 

5

Stage 

6

Summary of Contents for AX-ET-6

Page 1: ...0 230Vac 15 Inputs Sensor 10K3A1 See Axio temperature sensor range Remote Setpoint 1 11kΩ For 4 C or 20 C Setback volt free timer input Close contact to activate setback LCD Display 2 lines by 8 characters Temperature Range 20 C to 120 C Stage Selection CCCCCC CCCCCH CCCCHH CCCHHH CCHHHH CHHHHH HHHHHH C cooling H heating Setpoint 10 C to 110 C Offset 0 to 50 C Differential 0 to 12 C Setback Range ...

Page 2: ...y switching points to 2 C above the offset and 2 C below the offset MENU I NC DEC INC DEC I NC DEC Stage switching If the stage is set for cooling the relay will switch on when the temperature rises above the upper switching point and will switch off when the temperature falls below the lower switching point If the stage is set for heating the relay will switch on when the temperature falls below ...

Page 3: ...on whilst a dash is shown when the stage relay is off Minimum On and Off times This function prevents over cycling of the output For example setting the minimum on time to 5 seconds will ensure any output stage is in on for a minimum of 5 seconds The Off time works in a similar way When the Actual temperature display is visible press three times to display the On value Press or to adjust the param...

Page 4: ... Once the setpoint and switching requirements have been defined the stage offsets and stage differentials can be calculated For Stage 1 Cooling Stage Offset Stage mid point Setpoint 26 20 6 Stage Differential Switch on Switch off 28 24 4 The calculated values listed below should be entered using the set up menu Setup option Required value Stage select CCHHHH S1 Offset 6 C S1 Differential 4 C S2 Of...

Reviews: