Axima CONTIS basic User Instructions Download Page 4

4

BATTERY CHARGERS 

and

 POWER SUPPLIES 

for

 INDUSTRIAL APPLICATIONS

4 7390 00 0

STATION BATTERY CHARGER

Operating instructions

CON

T

IS

 

basic

4. Charger installation

                                                   
The box of the charger is intended to be hung on the wall (on a stand or on a bracket) in the vertical working position. However,  

the charger may be operated in the horizontal position, laid on its rear side, on a table or a base etc. To secure the correct functioning 
of the charger, it is necessary to keep the distance of at least 100 mm on both the sides of the charger as well as on the front side from 

other devices in order to provide sufficient ventilation. The slots for air suction must not be covered. With regard to the possibility of 
dust suction, the placement of the device on the floor or in a low position above the floor is not suitable. 

The charger cannot be used in an extremely dusty environment. The deterioration in cooling of internal parts could occur. The charger 
is equipped with a 5 wire cable 3N PE, in a one-phase design with a 3 wire cable 1 N PE ex-factory. The socket for the connection must 
be protected with a suitable circuit breaker. Output clamps for DC voltage can be found inside of the charger - claps are prepared for 
montage of external cables. Positive cable from the battery (usually red) fix to plus clamp, negative fix to minus clamp. For conducting 
DC cables into the charger, prepared grommets on the bottom of the charger can be used. Voltage dropping in the output cables 
during the charging should be taken into consideration - resistance of the cables should be set in the charger‘s menu.

        

5. Charger operation

5.1 Charger setting and connection to the battery

• 

prior to connection to the battery put the charger to the mains 

and press STOP button

• 

open the setting menu by press of right shifts together for  

5 seconds

• 

set the parameters (see menu bellow)

• 

leave the setting menu

• 

switch off the charger from the mains

• 

connect the battery and the load (control the battery voltage  

on display before you press START)

• 

connect to the mains and press START button

(run  time  for  leave  the  menu  is  1  min  of  inactivity;  all  changed 
parameters have to be saved by the SAVE button; parameters could be 
set during the operation, changed parameters are activated by leave 
the menu)