background image

 

 

 

Operation 

To refill the chlorinator 

1.  Isolate the chlorinator.   

Important:

  Close the 

supply valve BEFORE closing the return valve to 
prevent over-pressurization of the chlorinator.    

2.  Open the vacuum relief valve (Models 3075 & 

3150) to relieve vacuum. 

3.  Remove the lid. (Be careful not to inhale fumes.) 
4.  Fill the chlorinator with Axiall LLC Accu-Tab

®

 

Tablets. 

5.  Replace the lid, making sure the surfaces are 

clean and the O-ring is seated.     
(Models 3008C, 3012, 3075 & 3150.  Use 
silicone based oil ONLY for lubrication.) 

6.  Close the vacuum relief valve. 
7.  Open the return

 

valve first

then the

 

supply valve. 

 

To operate the chlorinator 

1.   Start flow through the chlorinator.  

Important:

  

Open the outlet valve BEFORE opening the inlet 
valve to prevent over-pressurization of the 
chlorinator. 

2.  Adjust the control valve to the desired setting.  

Check Available Chlorine regularly to determine 
the best setting. 

3.  Adjust the control valve and refill the chlorinator 

as needed to maintain chlorine levels. 

 

Note:  

When pool circulation stops, flow to the 

chlorinator will stop.  This will stop chlorine delivery. 
 
 

Cleaning 

The chlorinator should be cleaned twice per year to 
remove any residual product that may accumulate inside 
the unit.  Cleaning may be accomplished by soaking in a 
dilute acid solution.  Addition of muriatic acid will lower 
the pH of the water.  Be prepared to add a suitable pH 
increaser after cleaning is complete. 

 
 
 
 

 

Preparation for cleaning: 

1.  Have 2 gallons (24 fl. oz. for 3008C & 3012) of 

muriatic acid ready to add to the chlorinator.  
Wear rubber gloves and rinse all equipment 
thoroughly when finished. 

2.  Have a clean, empty container for storage of any 

tablets inside the chlorinator. 

3.  Always use appropriate safety equipment while 

servicing the chlorinator or handling chemicals. 

 

To clean the chlorinator while installed: 

1.  Isolate the chlorinator from the system by 

closing both the return and supply valves. 

2.  Remove the lid and remove all the tablets from 

the chlorinator.  Temporarily place these tablets 
in the clean, empty container. 

3.  Rinse the chlorinator with water and (with the lid 

removed) open the return valve temporarily to 
drain the chlorinator.   

4.  Close the return

 

valve

 

and

 

repeat step number 3. 

5.  Close the return valve and fill the chlorinator with 

water so there is about one inch of water above 
the sieve plate.  Using rubber gloves and other 
safety protection, carefully pour the muriatic acid 
into the chlorinator including the walls of the 
chlorinator.  

ALWAYS ADD ACID TO WATER, 

NEVER ADD WATER TO ACID.  

Leave the lid 

removed and do not breathe any fumes.  Let 
soak for 30 minutes.   

6.  After 30 minutes, open the return valve.  Open 

the supply valve and flush the chlorinator for 30 
minutes at 10-20 gpm (5 gpm on Models 3008C 
& 3012).   

7.  After 30 minutes of flushing, isolate the 

chlorinator and rinse the walls with water.  Drain 
the chlorinator by temporarily opening the return  
valve.  Rinse a second time and drain. 

8.  For models 3008C and 3012, rinse off the tablet 

canister and soak in muriatic acid to remove any 
residue, making sure all the holes are open.  
Rinse well with water when finished. 

9.  Cleaning is now complete.

 
 

Summary of Contents for Accu-Tab 3000 Series

Page 1: ...n Manual Revised 06 25 15 DANGER DO NOT MIX CHEMICALS The Accu Tab chlorinators are designed for use with Axiall approved tablets only Do not use Cal Hypo tablets with stabilized chlorine or bromine products or other sanitizing chemicals Fire or explosion could result ...

Page 2: ...ne to the chlorinator 6 Connect the return line in the same manner 7 Pipe sizes as follows Model Inlet Outlet 3008C 3012 1 3075 1 2 3150 3500 1 3 8 Restart the pump open the return service valve FIRST then open the supply service valve and control valve to establish flow through the chlorinator Check for leaks 9 Make sure the sieve plate is in its proper position resting in the groove 10 Installat...

Page 3: ...r 3008C 3012 of muriatic acid ready to add to the chlorinator Wear rubber gloves and rinse all equipment thoroughly when finished 2 Have a clean empty container for storage of any tablets inside the chlorinator 3 Always use appropriate safety equipment while servicing the chlorinator or handling chemicals To clean the chlorinator while installed 1 Isolate the chlorinator from the system by closing...

Page 4: ...4 ...

Page 5: ...5 ...

Page 6: ...l s Accu Tab calcium hypochlorite tablets are used in the Chlorinator If any of these conditions are not met this Limited Lifetime Warranty will not apply and you acknowledge and agree that your purchase of the Chlorinator will be on an AS IS basis without any warranty of any kind whatsoever having been provided by Axiall You assume all responsibility and risk and liability arising from i the unlo...

Reviews: