![Axi STS 6004 Operating & Maintenance Manual Download Page 22](http://html1.mh-extra.com/html/axi/sts-6004/sts-6004_operating-and-maintenance-manual_3036310022.webp)
REV03016704010220
21
Servicing Water Collection Drum:
1.
Keep a fuel waste container below the Manual Drain Port (Please see Step 3).
2.
Remove the Float Switch from the Water Collection Drum.
3.
Properly dispose contents of the Water Collection Drum in accordance with the proper AHJ.
4.
Replace the Float Switch to its original state on the Water Collection Drum.
5.
Continue to “Manual Servicing of Water Separator”.
Manual Servicing of Water Separator:
1.
Keep a fuel waste container under the Manual Drain Port.
2.
Open the bleed screw on top of the Water Separator to break vacuum.
3.
Open the AWD Isolation Ball Valve and Manual Drain Port.
a.
See “Servicing the Primary Filter/Water Separator” for additional info.
4.
Close the Manual Drain Port when all water has been drained from the Water Separator’s Sump.
5.
Open the system’s Inlet and Outlet Isolation Ball Valves.
6.
Confirm that the AWD Isolation Ball Valve and Manual Drain Ports are returned to their original positions.
7.
Return the enclosure door panel selector switch to its original position.
Summary of Contents for STS 6004