Tank Level Sensors (RMA-FTL1-SEN & RMA-FTL2-SEN, RMA-WTL1-SEN & RMA-WTL2-SEN)

Dual Switch Point

The Tank Level Sensors have a high and low switch point with a differential in between. 

While the float moves through the differential, its switch state remains unchanged until it 

hits the high or low point, as shown below. You may adjust the height of this differential 

by moving the weight closer to or further away from the float.

When the float switch 

is on its way up, the 

switch remains in the 

same state until it 

reaches the high point.

Differential

When the float switch 

is on its way down, 

the switch remains in 

the same state until it 

reaches the low point.

Differential

Install Your Tank Level Sensor

Do not use this sensor in hazardous (classified) locations or life safety applications. 

Step 1: Mount your Tank Level Sensor.

You may use the attached polypropylene hanging clamp to hang your Tank Level Sensor. 

The PVC-coated cable may be hung down a wall or in a corner of the tank—it does not 

have to be suspended from the center. Allow a swing radius for the float that is equal to 

the distance between the control weight and the face of the float.

Note that the height and depth (in feet and inches) at which the float switch changes state 

depends on two factors:

• 

the height at which the float is suspended in the tank by the hanging clamp

• 

the distance between the float face and the control weight (which creates the 

differential)

You may wish to experiment with different combinations to get the results you desire.

When considering the layout of your components, remember that the speaker wire cannot 

withstand the same conditions as the PCV-coated cable attached to the float. Do not run 

the speaker wire inside the tank or immerse it.