Flood Sensor - Spot

AVTECH

AVTECH’s Flood Sensor - Spot

 monitors the 

presence/absence of liquid on a flat surface. 

When liquid collects underneath the blue 

housing, it bridges the 2 adjustable-height 

contacts and trips the sensor. The contacts, 

which are 1" apart, arrive 1/32" off the ground, 

and adjust individually from 0" to 1/8" high. 

Self-adhesive feet on the bottom of the housing 

allow you to fasten the sensor to trouble-spots 

and also provide a gap to admit water to the 

contacts.

Flood Sensor - Spot Package Contents

•  One (1) Flood Sensor - Spot with 25' low-voltage 2-wire cable attached

•  One (1) 9V alkaline battery

Flood Sensor - Spot

Foot

Liquid

Foot

Housing

Surface

Contacts

1"

0" to 1/8" from surface

Install Your Flood Sensor - Spot

Do not use this sensor in hazardous (classified) locations or life safety applications. 

Step 1: Adjust the height of the contacts if necessary.

You may leave the contacts at the factory-adjusted height of 1/32" away from 

the floor, or adjust them between 0" and 1/8" high. To simulate the distance 

to the floor, rest a straight-edge on the feet closest to the contacts while you 

adjust them.

• 

Tighten the contacts clockwise to raise them farther away from the floor.

• 

Loosen the contacts counter-clockwise to lower them closer to the floor.

While you may lower the contacts flush to the floor (0" high), doing so 

increases the chance of a false alarm—mere dampness or a film of dirt could 

bridge the contacts. Metal, too, forms a complete circuit, so if you place the 

unit on a metal surface, be sure to maintain a gap under the contacts.

Summary of Contents for RMA-FS2-SEN

Page 1: ...Foot Housing Surface Contacts 1 0 to 1 8 from surface Install Your Flood Sensor Spot Do not use this sensor in hazardous classified locations or life safety applications Step 1 Adjust the height of the contacts if necessary You may leave the contacts at the factory adjusted height of 1 32 away from the floor or adjust them between 0 and 1 8 high To simulate the distance to the floor rest a straigh...

Page 2: ...d surface may form a seal and water won t reach the contacts until it s risen up the sides or over the top Step 4 Connect your Flood Sensor Spot to Room Alert Do not connect the switch sensor inputs dry contacts on AVTECH products to any live circuit Use only low voltage 2 wire cable to connect switch sensor inputs Your sensor comes with one end of a 25 low voltage 2 wire cable already attached Th...

Page 3: ...lip Sensor Features Specifications Environment Condition Monitored Presence absence of liquid Type Of Sensor Switch Normal State Closed Liquid not detected Alarm State Open Liquid detected Power Supply 9V alkaline battery Sensor Cable Type Low voltage two wire cable Included Yes Length 25 Maximum Extendible Length 900 Compatible Products Any Room Alert model or Wireless Sensor Hub AVT 171211 2 1 0...

Page 4: ...el you may leave the default Switch Sen X or enter something more descriptive of up to 15 characters You may use the following characters in sensor labels letters numbers spaces hyphens underscores _ and periods 4 In Alarm On select the alarm state Open or Closed for your switch sensor You may find the alarm state of your switch sensor under the Features Specifications section of this Installation...