Before stroking the actuator, please ensure that the process is safe to do so and that all
hands are kept away from the moving shaft / cams.
Stroke the actuator to the opposite end of travel. Set the top EasiFix self-locking cam by
pushing down and turning the EasiFix self-locking cam until the switch is activated.
See figure 6.
Before stroking the actuator, please ensure that the process is safe to do so and that all
hands are kept away from the moving shaft / cams.
Stroke the actuator from one end of travel to the other several times to check the switch
operation. If the switches require adjustment, repeat as required.
MAGNUM MECHANICAL NAMUR
Figure 6
5
Field Wiring
Field Wiring Terminal Strip:
10)
Blue wire Input (-) 4-20mA
9)
Brown wire Input (+) 4-20mA
8)
Yellow transmitter ( no polarity)
7)
Yellow transmitter ( no polarity)
Terminal screw torque: 2 – 3 in. lb. (0.22 - 0.3 Nm)
Wires must be rated at least 105
°
C with minimum 0.25mm thickness shall be used for external
connections.
See Controlled Diagram (Appendix A - page 18)
TOP CAM
PUSH DOWN,
TURN &
RELEASE
BOTTOM CAM
LIFT UP, TURN
& RELEASE