AVI AVI-PDU Series Installation And Operating Instructions Manual Download Page 3

 

 

2

SECTION 1 INTRODUCTION   

1.1 System Description   

This instruction manual is for the    AVI-PDU Series smart two  wire RF admittance level limit switch, which is used for 

most  level  measurements  and  control  and  is  suitable  for  almost  all  industrial  or  civil  applications  where  measuring  level  of 

liquids,  powders,  slurries  and  interface.  The  equipment  can  be  either  installed  indoor  or  outdoor,  no  special  mounting 

requirements needed.   

The  equipment  is  a  level  switch  comprised  of  one  electronic  unit,  one  connecting  coaxial  cable  and  one  rigid  or  cable 

sensing  element  (and  also  it  could  be  called  probe).    These  components  can  be  connected  in  an  integral  configuration  or  a 

remote configuration which all electrical components are mounted away from the measuring point and the sensing element. The 

sensing element can be manufactured of many different metals and insulators depending on the specific application. See figure 

1.1 as AVI-PDU series integral system scheme.   

 

Figure 1.1    AVI-PDU series RF level switch 

The AVI-PDU series RF level switch is strictly followed the International/Chinese standards which list below.

  

1.2 Operation Principle 

Radio Frequency admittance level technology uses a basic capacitance technology to detect the difference in materials, i.e. 

air/powder, air/liquid, oil/water. But it has advanced features for rejecting coatings, more reliable and stable operation, higher 
accuracy and remote electronics. 

Radio  Frequency  admittance  technology  employs  a  capacitance  bridge  and  differs  from  capacitance  technology  in  the 

electronics; cable and sensing element uses a driven shield circuit to stabilize the coaxial cable. The electronic unit

s measuring 

(probe) signal is also passed through a parallel in-phase amplifier internally. This additional signal is connected to the shield of 
the  coaxial  cable  and  then  is  passed  to  the  sensing  element

s  shield  connection.  This  driven  shield  amplifier  is  an  in-phase 

amplifier with a gain of 1. The signal on the shield has the same potential, phase, and frequency as the measuring signal but is 
electrically isolated from the measuring signal and measuring circuit. Since the center wire & shield wire of the coaxial cable 
have the above relationship, there is no potential difference between them. No potential difference means that no current flows 
between the conductors, and no current flow (leakage) from the center wire to the shield means there is no capacitance between 
them  (capacitance  equal  zero.)  As  a  result,  build-up  on  the  sensor,  cable  length  and  cable  temperature  have  no  affect  on  the 
measurement. A separate ground wire connects the probe ground to the electronic amplifier ground. 

Summary of Contents for AVI-PDU Series

Page 1: ...Installation and Operating Instructions Series AVI PDU RF DRIVEN SHIELD LEVEL SWITCH...

Page 2: ...ipment Total weight about 5 kg or higher with certain longer cable probes and over 15 kg with flanges 2 Be aware of the power and relay wiring when doing calibration or maintenance as high voltage can...

Page 3: ...etect the difference in materials i e air powder air liquid oil water But it has advanced features for rejecting coatings more reliable and stable operation higher accuracy and remote electronics Radi...

Page 4: ...be the impedance of the build up is low and measurable current will not pass from the measuring element to the shield or ground i e UA UB IAB UA UB YL 0 The electronic unit so only measures the curren...

Page 5: ...instrument failure Ambient Operating Temp electronics 40 75 40 167 Storage Temp 40 85 40 185 Response time 0 5second Time delay 2 25seconds continuously adjustable Barrier Built in limiting current t...

Page 6: ...optional PTFE NO 2 BSPT 2 NPT optional OD22mm 0 87 Threeterminal rod 100 1 0MPa 212 145psi 25 1 6MPa 77 232psi Heavyduty anti agitation 21 04ss st other optional UR NO 170mm 170mm 6 7 6 7 205mm 8 205...

Page 7: ...lt either the factory or local representative for specific recommendations Electrical connections should conform to plant and national standards For horizontal mounting instrument wire entries should...

Page 8: ...ystem mounting 4 4 Remote Installation A remote system separates the probe from the electronics with a special coaxial cable provided by factory The cable can be field shortened and re terminated as r...

Page 9: ...be to keep it out of the flow stream 3 Do not open sensing element or loosen sealed gland 4 Use open end wrench on the wrench flat to tighten sensing element Do Not use the housing as a source of leve...

Page 10: ...9 Anchor mounting Bent mounting Bracket mounting in open vessel External side arm mounting...

Page 11: ...10 15 Different Mounting Angle Flushing Mounting Silo Application...

Page 12: ...gure 4 5 below All of the sensing element connections are made to the terminals on the opposite side of the power and relay connections The shield wire red and the center wire blue are twisted be sure...

Page 13: ...ight hand entrance fitting into housing 3 Adjust the cable for suitable length 4 Connect the wires to the proper terminals and verify it is correct 5 Tighten the upper lid again Instrument uses normal...

Page 14: ...wiring the SETPOINT is the operating control used to control the switch point at which the relay changes state Turning the switch point adjustment clockwise increases the amount of sensed capacitance...

Page 15: ...nd place is at ON following is same factory setting always also at that position Range setting at on the top of the unit RANGE change the switch No 2 3 4position could measure different process materi...

Page 16: ...sulating Material 2 E Turn the set point adjustment slowly clockwise CW until relay once again just operates LED change to GREEN counting the number of revolutions required to change states or you com...

Page 17: ...DU level control If attempts to locate the difficulty fail notify your local FITECHNIC representative or call the factory directly Assure power to the equipment has been turned before opening the expl...

Page 18: ...without build up will have the following values Resistance higher than 1M at all test points consult factory Voltage lower than200mV at all test points consult factory DSH CW GND multimeter 7 2 Testin...

Page 19: ...ctronic unit malfunction Yellow LED f Replace unit g LED failed g Replace fuse of unit or turn power on again 2 Instrument never indicates alarm a Sensing element not seeing material HLFS a Need longe...

Reviews: