
Avaya
t
Line Interactive RM UPS Site Preparation, Installation and Operator’s Manual
S
164201663 Rev 1
55
Chapter 9
Troubleshooting
This section explains:
S
UPS alarms and conditions
S
How to silence an alarm
S
Site wiring fault on 120V models
S
Service and support
Audible Alarms and UPS Conditions
The UPS has an audible alarm feature to alert you of potential power
problems. Use Table 9 to determine and resolve the UPS alarms and
conditions.
On/Off Button
Test/Alarm Reset Button
Power On Indicator (green)
On Battery Indicator (yellow)
Overload Indicator (red)
Service Indicator (red)
Load Segment 2 Indicator (green)
Load Segment 1 Indicator (yellow)
Lit
Flashing
Unlit
Indicator Legend
Figure 29. Alarm Indicators
Silencing an Audible Alarm
Before silencing an alarm, check the alarm condition and perform the
applicable action to resolve the condition (see Table 9). To silence the
alarm for an existing fault, press the
button. If UPS status changes,
the alarm beeps, overriding the previous alarm silencing.