port. If that doesn’t bring the total power into the power budget, power is removed from the next highest
physical port and so until requested power is within the capability of the internal power supply.
The C360 series of Avaya switches have similar commands to the P330. The
“show powerinline”
command display is slightly different from the P330 in that it doesn’t show the power allocated class
column. Again, Avaya switches, Mid-Spans and gateway power schemes do not require or rely on an
advertised class of power.
All ports have power enabled by default. Commands are:
Enable or disable
power to a port or group of ports
Set port powerinline <mod/port> enable | disable
Assign a priority
in case over-subscription requires shutting down port power
Set port powerinline priority <mod/port> <priority>
Low
– (Default setting) standard priority for standard devices
High
– higher priority than low for important devices
Critical
– highest priority for critical devices like APs
Describe the PD for each port
Set port powerinline type <mod/port> “string”
The string is a text description of the PD.